| Plan Review Notes For Permit 15080518 |
| Permit Number |
15080518 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-17 16:12:18 | SEPARATE PERMIT REQUIRED FOR COMMUNICATION CONNECTION | | | TO ENERGY MANAGEMENT SYSTE, PER THE NOTE ON THE PLAN. | | | | | | | | | EQUIPMENT GROUND WIRE SIZES AND GROUNDING ELECTRODE | | | CONDUCTOR ARE TO SIZED PER 250.66 AND 250.122. THE | | | DRAWING SHOWS EGC AND GES CONDUCTORS WITHOUT THE | | | BENEFIT OF PHASE CONDUCTORS OR OCP. | | | | | | |
|