2015-10-07 11:34:082ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080487
 10/7/15
  
 1) PLEASE REVIEW COMMENT #10 FROM THE1ST REVIEW
 REGARDING THE TRANSFER GRILLES RETURNING AIR INTO THE
 CORRIDORS. THE PLAN IS NOT IN COMPLIANCE WITH SECTION
 601.2 FBC-14 MECHANICAL: AIR MOVEMENT IN EGRESS
 ELEMENTS-
 CORRIDORS SHALL NOT SERVE AS SUPPLY, RETURN, EXHAUST,
 RELIEF OR VENTILATION AIR DUCTS.
  