2015-10-15 11:44:05PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET AT EVERY PEDESTRIAN DOOR, NOT JUST THE FRONT
 DOOR. A LACK OF THE REQUESTED SITE PLAN MAKES IT
 DIFFICULT TO VERIFY OR CONFIRM WHICH DOOR MAY LEAD TO A
 SERVICE CORRIDOR THUS NOT REQUIRING SIGNAGE.
 2. NEC 406.9(B) REQUIRES THAT IN ADDITION TO THE IN-USE
 TYPE COVER, ALL OUTLETS IN WET LOCATIONS TO BE LISTED
 OR RATED AS WEATHER RESISTANT "WR".
 3. FBC-ENERGY CONSERVATION SECTION C405 HAS SPECIFIC
 LIGHTING CONTROL REQUIREMENTS WHICH SHALL BE ADHERED
 TO.
 4. NEC 408.4(A) REQUIRES A SITE SPECIFIC/ACCURATE
 CIRCUIT DIRECTORY. THIS DIRECTORY HAS TO MATCH THE
 FLOOR PLAN.
 5. NEC 408.4(B) REQUIRES THAT THE PANEL BE MARKED WITH
 THE LOCATION OF THE SOURCE OF POWER.
 6. NEC 2154.5 REQUIRES THAT YOU PROVIDE A FEEDER
 DIAGRAM SHOWING CONDUCTOR SIZING AND LOAD CALCS. THESE
 LOAD CALCS ARE BASED ON THE CONNECTED LOADS TO EACH
 PANEL, THUS THE NEED FOR ACCURATE PANEL SCHEDULES.
  
 CORRECT THE ITEMS DESCRIBED ABOVE AS INSTRUCTED AND
 RE-SUBMIT THE DRAWINGS FOR ANOTHER REVIEW.
  
 WHEN RESUBMITTING, YOU SHALL PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH COMMENT ITEM ALONG WITH THE
 CITY?S RE-SUBMITTAL FORM. SEE LINK BELOW:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 ADDITIONALLY, IT IS REQUIRED THAT YOU INSERT THE
 CORRECTED PAGES INTO THE DENIED SUBMITTAL PACKAGE. MARK
 VOID ON THE PREVIOUSLY REVIEWED SHEETS AND LEAVE THEM
 IN FOR COMPARATIVE REVIEW.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  