Plan Review Notes
Plan Review Notes For Permit 15080487
Permit Number 15080487
Review Stop P
Sequence Number 1
Notes
Date Text
2015-08-21 06:52:191) SHOW THE REQUIRED CLEAR FLOOR SPACES FOR THE
 LAVATORY AND THE WATER CLOSETS IN THE TOILET ROOMS IN
 ACCORDANCE WITH THE 2014 FBC-ACCESSIBILITY SEC.604.3.1,
 606.2,606.3 & SEC. 306.2.
 2) THE BREAK ROOM SINK SHALL COMPLY WITH THE
 FBC-ACCESSIBILITY SEC.606.2.
 3) THE WIDTH OF THE SINGLE USER TOLET ROOMS SHALL BE A
 MINIMUM 85 INCHES WIDE IF BUILT PERFECT. 86 INCHES
 ALLOWS FOR TOLERANCES.
 4) SHOW THE FIXTURE CLEARANCES FOR THE WATER CLOSET IN
 THE TOILET ROOMS. COMPLY WITH FBC-ACCESSIBILITY
 SEC.604.2.
 5) IDENTIFY THE TOILET ROOM WITH JUST THE URINAL.
 6) INDICATE THE TYPE OF OCCUPANCY OF THIS SPACE IN
 ACCORDANCE WITH 2014 FBC SEC.302.1.
 7) INDICATE THE SQUARE FOOTAGE OF THE SPACE AND THE
 OCCUPANT LOAD IN ACCORDANCE WITH THE 2014 FBC TABLE
 1004.1.2
 8) SUBMIT DETAILS FOR THE MOUNTING HEIGHTS FOR ALL
 HANDICAP ACCESSORIES LOCATED IN THE TOILET ROOMS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 9) SUBMIT MANUF.SPECIFICATIONS FOR THE TANKLESS WATER
 HEATER. WPB AMEND. TO FBC SEC. 107.2.1.
 10) A DRINKING FOUNTAIN IS REQUIRED IN THIS SPACE PER
 TABLE 403.1 OF 2014 FBC-PLUMBING. A MINIMUM OF TW
 DRINKING FOUNTAINS SHALL BE PROVIDED PER THE 2014
 FBC-ACCESSIBILITY SEC.211.2.
 11) SHT.#4 - DOMESTIC WATER RISER - THERE IS A 1" LINE
 SUPPLYING AN UNIDENTIFIED FIXTURE. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  