Plan Review Notes
Plan Review Notes For Permit 15080487
Permit Number 15080487
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-20 09:13:581ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080487
 8/20/15
  
 1) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROPOSED PROJECT.
 2) PROVIDE THE LEVEL OF ALTERATION ON THE PLAN IN
 COMPLIANCE WITH SECTION 501 FBC-14 EXISTING BUILDING
 CODE. THE SUBMITTED PLANS APPEAR TO INDICATE A LEVEL II
 ALTERATION THEREFORE MY REVIEW WILL BE IN ACCORDANCE
 WITH CHAPTER 8, AND THE FBC-14 MECHANICAL CODE.
 3) REFER TO SECTION 809 FBC-14 FBC-14 EXISTING BUILDING
 CODE:
 809.1 RECONFIGURED OR CONVERTED SPACES.
 ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND ALL
 SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE IN
 ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR
 MECHANICAL VENTILATION IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL.
 EXCEPTION: EXISTING MECHANICAL VENTILATION SYSTEMS
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 809.2.
  
 809.2 ALTERED EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
  
 IN REFERENCE TO THE ABOVE SECTIONS PROVIDE VENITLATION
 CALCULATIONS FOR ALL ROOMS AND SPACES- INCLUDING A
 SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED CFM'S OF
 O/A AIR.
  
 4) SHEET 5: PROVIDE A SCOPE OF WORK FOR MECHANICAL
 DEMOLITION AND MECHANICAL ALTERATIONS WITH KEY NOTES
 AND CORRESPONDING DETAILS ON THE PLAN. CLARIFY IF THE
 ENTIRE AC SYSTEMS ARE BEING REPLACED, OR IF THE AIR
 HANDLERS ALONE ARE BEING RELOCATED- NO INFORMATION IS
 PROVIDED. PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS
 AND LABEL THE UNITS AS NEW OR EXISTING. PLEASE NOTE
 THAT COOLING AND HEATING LOAD CALCULATIONS ARE REQUIRED
 FOR NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 5) SHEET 5: REFER TO SECTION 603.1.1 FBC-14 MECHANICAL
 CODE AND SHOW COMPLIANCE:
 603.1.1 SPACE PROVIDED.
 SUFFICIENT SPACE SHALL BE PROVIDED ADJACENT TO ALL
 MECHANICAL COMPONENTS LOCATED IN OR FORMING A PART OF
 THE AIR DISTRIBUTION SYSTEM TO ASSURE ADEQUATE ACCESS
 FOR (1) CONSTRUCTION AND SEALING IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 603.1 OF THIS CODE; (2)
 INSPECTION; AND (3) CLEANING AND MAINTENANCE. A MINIMUM
 OF 4 INCHES (102 MM) IS CONSIDERED SUFFICIENT SPACE
 AROUND AIR HANDLING UNITS.
 EXCEPTION: RETROFIT OR REPLACEMENT UNITS NOT PART OF A
 RENOVATION ARE EXEMPT FROM THE MINIMUM CLEARANCE
 REQUIREMENT.
 6) SHEET 5: REFER TO SECTION 602 AND PROVIDE NOTES AND
 DETAILS INCDICATING COMPLIANCE FOR ALL MATERIALS
 FORMING THE PLENUM CLOSET AND ALL MATERIALS CONTAINED
 WITHIN IT INCLUDING THE CLOSET DOORS, WALLS, CEILING,
 AND ALL COMPONENTS OF THE AIR HANDLERS INCLUDING
 ELECTRICAL WIRING, PLUMBING PIPING, AND INSULATIONS.
 7) SHEET 5: PROVIDE AN AIR DISTRIBUTION SCHEDULE
 LISTING THE MAKES AND MODEL NUMBERS IOF THE SUPPLY
 DIFFUSERS AND RETURN GRILLS.
 8) SHEET 5: REFER TO SECTION C403.2.7 (INCLUDING TABLES
 AND SUB-SECTIONS): PROVIDE DETAILS FOR DUCT
 INSTALLATIONS INCLUDING THE TYPE OF DUCTS, AND SUPPORT,
 CONNECTION, AND SEALING DETAILS AND SPECIFICATION.
 9) SHEET 5: PROVIDE EQUIPMENT SCHEDULES FOR THE TOILET
 ROOM EXHAUST FANS.
 10) SHEET 5: REFER TO SECTION 601.2 AND CORRECT THE
 PLAN THE RETURN AIR SYSTEM ACCORDINGLY- AIR MOVEMENT IN
 EGRESS ELEMENTS:
 CORRIDORS SHALL NOT SERVE AS SUPPLY, RETURN, EXHAUST,
 RELIEF OR VENTILATION AIR DUCTS.
 EXCEPTIONS:
 1. USE OF A CORRIDOR AS A SOURCE OF MAKEUP AIR FOR
 EXHAUST SYSTEMS IN ROOMS THAT OPEN DIRECTLY ONTO SUCH
 CORRIDORS, INCLUDING TOILET ROOMS, BATHROOMS, DRESSING
 ROOMS, SMOKING LOUNGES AND JANITOR CLOSETS, SHALL BE
 PERMITTED, PROVIDED THAT EACH SUCH CORRIDOR IS DIRECTLY
 SUPPLIED WITH OUTDOOR AIR AT A RATE GREATER THAN THE
 RATE OF MAKEUP AIR TAKEN FROM THE CORRIDOR.
 2. WHERE LOCATED WITHIN A DWELLING UNIT, THE USE OF
 CORRIDORS FOR CONVEYING RETURN AIR SHALL NOT BE
 PROHIBITED.
 3. WHERE LOCATED WITHIN TENANT SPACES OF 1,000 SQUARE
 FEET (93 M2) OR LESS IN AREA, USE OF CORRIDORS FOR
 CONVEYING RETURN AIR IS PERMITTED.
 4. INCIDENTAL AIR MOVEMENT FROM PRESSURIZED ROOMS
 WITHIN HEALTH CARE FACILITIES, PROVIDED THAT THE
 CORRIDOR IS NOT THE PRIMARY SOURCE OF SUPPLY OR RETURN
 TO THE ROOM.
 11) PLEASE NOTE THAT ADDITIONAL COMMENTS MAY OCCUR UPON
 REVIEW OF CORRECTED AND RE-SUBMITTED PLANS.
  