| 2015-09-29 11:14:53 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE |
| | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE |
| | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED |
| | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. YOU SHALL PROVIDE A SITE PLAN INDICATING IF THIS |
| | STRUCTURE IS STAND ALONE, OR AN INTERIOR PORTION OF A |
| | LARGER AREA. |
| | 2. THE WALL HUNG WATER HEATER REQUIRES A DISCONNECT AS |
| | INDICATED BY NEC 422.30. |
| | 3. THE ELECTRIC WATER COOLER SHALL BE ON A GFCI |
| | PROTECTED CIRCUIT AS PER NEC 422.52 |
| | 4. A DEDICATED SIGN OUTLET ABOVE EVERY PEDESTRIAN ENTRY |
| | DOOR IS REQUIRED PER NEC 600.5. |
| | 5. MISSING EXIT LIGHT IN ENG. 4 OFFICE PER FBC 5TH |
| | EDITION 2014. |
| | 6. CEILING LUMINAIRES OUTLET BOXES SHALL BE LISTED TO |
| | SUPPORT A MINIMUM OF 50# PER NEC 314.27. |
| | 7. THE FLOOR PLAN REFLECTS THREE PANELS W/O ANY |
| | INDICATION AS TO THEIR RESPECTIVE OCCUPANCY AND NO |
| | METERS, YET THE ELECTRICAL RISER DIAGRAM SHOWS |
| | SOMETHING DIFFERENT. YOU SHALL SUBMIT A SITE SPECIFIC |
| | RISER DIAGRAM SHOWING CONDUCTOR SIZING AND INSULATION |
| | AS WELL THE SERVICE GROUNDING SYSTEM AS PER NEC 215.5 |
| | 8. YOU SHALL SUBMIT SITE SPECIFIC LOAD CALCS AS |
| | INDICATED IN NEC 220.16 |
| | 9. YOU SHALL IDENTIFY ALL PANELS ON THIS SERVICE AND |
| | INDICATE THEIR RESPECTIVE LOCATIONS ON THE FLOOR PLAN. |
| | PROVIDE A PANEL SCHEDULE FOR EVERY PANEL WITHIN YOUR |
| | PREMISES AS REQUIRED BY NEC 408.4 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |