| Date |
Text |
| 2015-08-28 14:49:22 | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15080487 |
| | ADD: 2749 EXCHANGE CT. |
| | CONT: RPM & M GENERAL CONTRACTORS |
| | TEL: (954)649-5304 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY AUGUST 28/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS NEED TO IDENTIFY TO WHAT CODE THEY WERE |
| | DESIGNED TOO? NOTE JUNE 30/ 2015 WAS THE 1ST DAY THE |
| | 2014 FBC-B WAS ADOPTED STATEWIDE. |
| | |
| | 2) THE DESIGNER OF RECORD WILL NEED TO SHOW TO WHICH |
| | COMPLIANCE METHOD THE PLANS WERE DESIGNED TO UNDER THE |
| | 2014 EBC-EXISTING BUILDING CODE. 301.1. |
| | |
| | 3) THE PLANS ARE MISSING THE 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS, |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS |
| | OCCUPANCY |
| | MINIMUM BUILDING TYPE |
| | SQUARE FEET OF BUILDING PER FLOOR |
| | FIRE SPRINKLERED OR NOT/ REQUIRED OR NOT |
| | OCCUPANCY LOAD |
| | |
| | 3) THE PLANS SHOW ALL NEW WINDOWS AND DOORS ARE BEING |
| | INSTALLED IN THE EXISSTING OPENINGS. PLEASE SHOW |
| | COMPLIANCE WITH 2014 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5) THE PLANS ARE MISSING THE WIND DESIGN CRITERIA. 2014 |
| | FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 5.2. RISK CATEGORY. |
| | |
| | 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | 6) SHEET # 2 INDICATES THE USE OF 2 INCH MOVEABLE |
| | PARTITIONS. NOTE THERE IS NO HEIGTH GIVEN FOR THESE |
| | PARTITIONS. COMPLIANCE WITH FBC-B TABLE 1604.3 FOOTNOTE |
| | B, CODE COMPLIANCE CAN NOT BE DETERMINED, IF REQUIRED. |
| | |
| | 7) THE NEW RESTROOMS DO NOT MEET THE REQUIREMENTS OF |
| | 2014 FBC-ACCESSIBILITY 604.3.1 AND FIGURE 604.3.1. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |