Plan Review Notes
Plan Review Notes For Permit 15080487
Permit Number 15080487
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-28 14:49:22 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080487
 ADD: 2749 EXCHANGE CT.
 CONT: RPM & M GENERAL CONTRACTORS
 TEL: (954)649-5304
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY AUGUST 28/ 2015
 ACTION: DENIED
  
 1) THE PLANS NEED TO IDENTIFY TO WHAT CODE THEY WERE
 DESIGNED TOO? NOTE JUNE 30/ 2015 WAS THE 1ST DAY THE
 2014 FBC-B WAS ADOPTED STATEWIDE.
  
 2) THE DESIGNER OF RECORD WILL NEED TO SHOW TO WHICH
 COMPLIANCE METHOD THE PLANS WERE DESIGNED TO UNDER THE
 2014 EBC-EXISTING BUILDING CODE. 301.1.
  
 3) THE PLANS ARE MISSING THE 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS,
 107.3.5.1.1 COMMERCIAL BUILDINGS
 OCCUPANCY
 MINIMUM BUILDING TYPE
 SQUARE FEET OF BUILDING PER FLOOR
 FIRE SPRINKLERED OR NOT/ REQUIRED OR NOT
 OCCUPANCY LOAD
  
 3) THE PLANS SHOW ALL NEW WINDOWS AND DOORS ARE BEING
 INSTALLED IN THE EXISSTING OPENINGS. PLEASE SHOW
 COMPLIANCE WITH 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) THE PLANS ARE MISSING THE WIND DESIGN CRITERIA. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 6) SHEET # 2 INDICATES THE USE OF 2 INCH MOVEABLE
 PARTITIONS. NOTE THERE IS NO HEIGTH GIVEN FOR THESE
 PARTITIONS. COMPLIANCE WITH FBC-B TABLE 1604.3 FOOTNOTE
 B, CODE COMPLIANCE CAN NOT BE DETERMINED, IF REQUIRED.
  
 7) THE NEW RESTROOMS DO NOT MEET THE REQUIREMENTS OF
 2014 FBC-ACCESSIBILITY 604.3.1 AND FIGURE 604.3.1.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  