| Plan Review Notes For Permit 15080427 |
| Permit Number |
15080427 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-17 15:20:39 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15080427 | | | 8/17/15 | | | | | | 1) SHEET M2.1: FIRE DAMPERS MISSING FOR DUCTS | | | PENETRATING RATED WALLS AT: (OPEN OFFICE 100/MECHANICAL | | | ROOM), (COMMON CORRIDOR/MECHANICAL ROOM), (OPEN OFFICE | | | 110/COMMON CORRIDOR), (OPEN OFFICE 130/COMMON | | | CORRIDOR), AND (ATRIUM/COMMON CORRIDOR). | | | 2) M2.1: PLEASE INCLUDE THE DAMPERS IN THE KEY NOTES, | | | AND PROVIDE AN EQUIPMENT SCHEDULE AND INSTALLATION | | | DETAILS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|