Plan Review Notes
Plan Review Notes For Permit 15080423
Permit Number 15080423
Review Stop E
Sequence Number 1
Notes
Date Text
2015-09-10 19:34:42PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 SCOTT, AS SIMPLE AS THIS SYSTEM MAY SEEM TO BE, NONE
 THE LESS, IT IS A FIRE ALARM SYSTEM AND THUS HAS
 SPECIFIC SUBMITTAL REQUIREMENTS BY THE FLORIDA BUILDING
 CODE 5TH EDITION 2014. SECTION 907.
 IN ADDITION TO THAT YOU NEED TO INDICATE HOW WILL THIS
 SYSTEM BE INTERCONNECTED WITH THE HOOD SYSTEM. CODE
 REQUIRES THAT THE FUEL TO THE COOKING APPARATUS BE SHUT
 DOWN IN THE EVENT OF AN ALARM, IS THAT BEING
 ACCOMPLISHED DIRECTLY FROM THE HOOD MECHANISM OR WILL
 IT BE VIA THE FIRE ALARM.
 THE PLANS SHALL HAVE AN INDICATION AS TO THE LOCATION
 OF THE OCPD FOR THE FACP.
 THE CODE REQUIRES THAT THE DRAWINGS BEAR THE NAME AND
 SIGNATURE OF WHOEVER DESIGNED/DREW THE PLANS.
 YOU PROVIDED SPEC SHEET FOR AN ANNUNCIATOR AND DIDN'T
 SHOW IT ON THE RISER, YET SHOWN IS A CELL TRANSMITTER
 AND NO SPEWC SHEET IS PROVIDED FOR IT.
 BE MORE SPECIFIC ON THE SCOPE AND INCLUDE IT ON THE
 DRAWINGS AS WELL.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME DIRECTLY.
  