Plan Review Notes
Plan Review Notes For Permit 15080415
Permit Number 15080415
Review Stop G
Sequence Number 2
Notes
Date Text
2016-01-13 10:26:071) FYI - THE GAS PERMIT SHALL BE DONE UNDER A SEPARATE
 PERMIT WITH A SEPARATE PERMIT APPLICATION.SINCE THE GAS
 INFORMATION AND DRAWINGS HAVE BEEN SUBMITTED A REVIEW
 WILL BE PERFORMED ON THE DOCUMENTS.
 2) THE ARCHITECTURAL PLAN A-100 SHOWS THE FIREPLACE AS
 GAS BUT IT IS NOT SHOWN ON THE GAS RISER OR ON THE GAS
 PLAN VIEW DRAWING. CLARIFY.
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS APPLIANCES. THE SPECIFICATION SHEETS SHALL CLEALY
 SHOW THAT THE APPLIANCES ARE LISTED AND LABELED IN
 ACCORDANCE WITH THE 2014 FBCR SEC.G2404.3. 2ND REQUEST.
 4) SHOW THE CORRESPONDING EHD FOR EACH SIZE OF CSST.THE
 DIFFERENT EHD NUMBERS CARRY DIFFERENT BTU LOADS.2ND
 REQUEST.
 5) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYERS
 LOCATED IN THE LAUNDRY ROOMS. REFER TO 2014
 FBC-RESIDENTIAL SEC. G2407.1. NOTE: THERE IS AN E-MAIL
 IN THE DOCUMENTS FROM A DANIEL DOLBEE THAT STATES THE
 RANGE IS 154,00 BTU'S BUT THE GAS DRAWING SHOWS THE
 RANGE AS 108,000 BTU'S .CLARIFY.
 6) THE 2 PSI LINE TO THE GENERATOR, POOL HEATER AND
 TANKLESS WATER HEATER IS SHOWN AS PE PIPE ON THE PLAN
 DRAWING AND AS CSST ON THE RISER DIAGRAM. WHICH IS IT?
 IF CSST, IT IS UNDERSIZED. CLARIFY.
 7) SIZE THE GAS BRANCCH LINES TO THE GENERATOR,POOL
 HEATER AND TANKLESS WATER HEATER. WPB AMEND. TO FBC
 SEC. 107.3.5.3.
 8) SIZE ALL SECTIONS OF THE UNDERGROUND GAS PIPING
 SYSTEM ON THE RISER DIAGRAM.
 9) IDENTIFY THE COOKTOP ON THE GAS RISER AND SHOW THE
 BTU LOAD OF THE APPLIANCE.WPB AMEND. TO FBC SEC.
 107.3.5.3.
 10) SHOW THE LENGTH OF THE SECTION OF PIPE RISING UP
 INTO THE CEILING. WPB AMEND. TO FBC SEC. 107.3.5.3.
 11) SHOW THE LENGTH OF ALL DROPS TO THE APPLIANCES AND
 THE LENGTH OF THE SECTION OF PIPE TO THE 2ND FLOOR. IT
 APPEARS LIKE THE TOTAL DEVELOPED LENGTH WILL EXCEED 100
 FEET.
 12) THE 1/2 PSI GALVANIZED PIPING UP TO THE CEILING IS
 UNDERSIZED.
 13) SHOW THE LENGTH OF EACH CUT SECTION OF PIPE ON THE
 RISER DIAGRAM. 2014 FBCR SEC. G2413.4.
 14) THE GREEN MARKER USED ON THE SIZING TABLE HAS MADE
 THE NUMBERS ON THE TABLES ILLEGIBLE. SUBMIT CLEAN
 SIZING TABLES.
 15) SHT. A-100 SHOWS THE TANKLESS WATER HEATER IN A
 WEATHERPROOF ENCLOSURE. SUBMIT DETAILS ON THE WATER
 HEATER AS TO HOW COMBUSTION AIR AND EXHAUST WILL
 ADDRESSED. WILL BE PROVIDED.
  