| Date |
Text |
| 2016-01-13 10:26:07 | 1) FYI - THE GAS PERMIT SHALL BE DONE UNDER A SEPARATE |
| | PERMIT WITH A SEPARATE PERMIT APPLICATION.SINCE THE GAS |
| | INFORMATION AND DRAWINGS HAVE BEEN SUBMITTED A REVIEW |
| | WILL BE PERFORMED ON THE DOCUMENTS. |
| | 2) THE ARCHITECTURAL PLAN A-100 SHOWS THE FIREPLACE AS |
| | GAS BUT IT IS NOT SHOWN ON THE GAS RISER OR ON THE GAS |
| | PLAN VIEW DRAWING. CLARIFY. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL |
| | GAS APPLIANCES. THE SPECIFICATION SHEETS SHALL CLEALY |
| | SHOW THAT THE APPLIANCES ARE LISTED AND LABELED IN |
| | ACCORDANCE WITH THE 2014 FBCR SEC.G2404.3. 2ND REQUEST. |
| | 4) SHOW THE CORRESPONDING EHD FOR EACH SIZE OF CSST.THE |
| | DIFFERENT EHD NUMBERS CARRY DIFFERENT BTU LOADS.2ND |
| | REQUEST. |
| | 5) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYERS |
| | LOCATED IN THE LAUNDRY ROOMS. REFER TO 2014 |
| | FBC-RESIDENTIAL SEC. G2407.1. NOTE: THERE IS AN E-MAIL |
| | IN THE DOCUMENTS FROM A DANIEL DOLBEE THAT STATES THE |
| | RANGE IS 154,00 BTU'S BUT THE GAS DRAWING SHOWS THE |
| | RANGE AS 108,000 BTU'S .CLARIFY. |
| | 6) THE 2 PSI LINE TO THE GENERATOR, POOL HEATER AND |
| | TANKLESS WATER HEATER IS SHOWN AS PE PIPE ON THE PLAN |
| | DRAWING AND AS CSST ON THE RISER DIAGRAM. WHICH IS IT? |
| | IF CSST, IT IS UNDERSIZED. CLARIFY. |
| | 7) SIZE THE GAS BRANCCH LINES TO THE GENERATOR,POOL |
| | HEATER AND TANKLESS WATER HEATER. WPB AMEND. TO FBC |
| | SEC. 107.3.5.3. |
| | 8) SIZE ALL SECTIONS OF THE UNDERGROUND GAS PIPING |
| | SYSTEM ON THE RISER DIAGRAM. |
| | 9) IDENTIFY THE COOKTOP ON THE GAS RISER AND SHOW THE |
| | BTU LOAD OF THE APPLIANCE.WPB AMEND. TO FBC SEC. |
| | 107.3.5.3. |
| | 10) SHOW THE LENGTH OF THE SECTION OF PIPE RISING UP |
| | INTO THE CEILING. WPB AMEND. TO FBC SEC. 107.3.5.3. |
| | 11) SHOW THE LENGTH OF ALL DROPS TO THE APPLIANCES AND |
| | THE LENGTH OF THE SECTION OF PIPE TO THE 2ND FLOOR. IT |
| | APPEARS LIKE THE TOTAL DEVELOPED LENGTH WILL EXCEED 100 |
| | FEET. |
| | 12) THE 1/2 PSI GALVANIZED PIPING UP TO THE CEILING IS |
| | UNDERSIZED. |
| | 13) SHOW THE LENGTH OF EACH CUT SECTION OF PIPE ON THE |
| | RISER DIAGRAM. 2014 FBCR SEC. G2413.4. |
| | 14) THE GREEN MARKER USED ON THE SIZING TABLE HAS MADE |
| | THE NUMBERS ON THE TABLES ILLEGIBLE. SUBMIT CLEAN |
| | SIZING TABLES. |
| | 15) SHT. A-100 SHOWS THE TANKLESS WATER HEATER IN A |
| | WEATHERPROOF ENCLOSURE. SUBMIT DETAILS ON THE WATER |
| | HEATER AS TO HOW COMBUSTION AIR AND EXHAUST WILL |
| | ADDRESSED. WILL BE PROVIDED. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |