Plan Review Notes
Plan Review Notes For Permit 15080415
Permit Number 15080415
Review Stop B
Sequence Number 2
Notes
Date Text
2016-01-22 13:37:59PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (NEW COMMENT) THE PERMIT APPLICATION IS MISSING FROM
 THE RESUBMITTAL. IF THE ORIGINAL IS NOT LOCATED A
 REPLACEMENT WILL BE REQUIRED.
  
 2) (PREVIOUS COMMENT) THE ENERGY COMPLIANCE FORMS
 SPECIFY R-20 CEILING INSULATION AND PLAN SHEET A-302
 HAS R-19 CEILING INSULATION. FBC 107.2.1
  
 3) (PREVIOUS COMMENT) THE REFERENCES TO THE STANDARDS
 ON SHEET S-1 ARE INCORRECT. THEY SHOULD BE AS FOLLOWS:
 ACI 318-11, ACI 530-11, ACI 530.1-11, ASCE 5-11, ASCE
 6-11, TMS 402-11 AND TMS 602-11. THE 2011 EDITIONS OF
 THESE STANDARDS ARE THE ONES THAT ARE REFERENCED IN
 CHAPTER 46 THE FBC FIFTH EDITION (2014).
  
 4) (NEW COMMENT) THE COMPONENT AND CLADDING PRESSURES
 FOR THE WALL AREAS ON SHEET S-1 ARE LOW FOR A TWO STORY
 STRUCTURE (25' MEAN ROOF HEIGHT) LOCATED IN EXPOSURE C.
 FBC-R301.2.1
  
 5) (PREVIOUS COMMENT) THE WEST ELEVATION DOES NOT MATCH
 THE FLOOR PLANS. THE EXTERIOR DOOR (ED 109) TO THE
 MASTER BATH IS SHOWN AS A WINDOW AND A WINDOW IS
 MISSING. THE SECOND FLOOR PLAN HAS TWO WINDOWS AND THE
 ELEVATION HAS THREE. FBC 107.2.1 SEE SHEETS A-100,
 A-101, A-201 AND S-7
  
 6) (PREVIOUS COMMENT) ADDITIONAL INFORMATION IS
 REQUIRED FOR THE MASONRY FIREPLACE AND CHIMNEY TO SHOW
 THAT IT WILL COMPLY WITH FBC R1001. PROVIDE DIMENSIONS
 AND DETAILS OF ALL PARTS AND COMPONENTS. FBC 107.2.1
 PROVIDE FIREBOX, DAMPER, SMOKE CHAMBER DIMENSIONS AND
 FLUE DIMENSIONS.
  
 7) (PREVIOUS COMMENT) FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. NO
 PRODUCT APPROVALS WERE SUBMITTED FOR THE EXTERIOR DOORS
 OR WINDOWS. THE NOA NUMBERS ON THE LETTER FROM THE
 ARCHITECT DO NOT MATCH THE ONES THAT WERE SUBMITTED.
 ALSO, LIST ALL OF THE PRODUCT APPROVALS ON ONE LETTER.
  
 8) (PREVIOUS COMMENT) SUBMIT TWO SETS OF THE PRODUCT
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FOR THE
 SPRAY FOAM INSULATION. FBC - R 316 SUBMIT THE PRODUCT
 EVALUATION REPORT FOR THE ICYNENE SPRAY FOAM.
  
 9) (PREVIOUS COMMENT) SUBMIT PRODUCT APPROVALS,
 MANUFACTURES' SPECIFICATIONS WITH INSULATION
 INSTRUCTIONS FOR THE COLONIAL AND BAHAMA SHUTTERS SHOWN
 ON THE ELEVATION DRAWINGS. FBC 107.2.1 & R301.2.1 THE
 PRODUCT APPROVAL FOR THE BAHAMA SHUTTERS IS EXPIRED AND
 NOTHING WAS SUBMITTED FOR THE COLONIAL SHUTTERS.
  
  
  
  
  
  