Plan Review Notes
Plan Review Notes For Permit 15080415
Permit Number 15080415
Review Stop G
Sequence Number 1
Notes
Date Text
2015-08-21 02:54:061) IDENTIFY THE MODEL OF THE GENERATOR ON THE GENERAC
 SPEC. SHEETS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE LOCATION OF THE POOL HEATER AND GENERATOR
 ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE GENERATOR IS NOT SHOWN ON THE GAS DRAWING OR
 INCLUDED IN THE DESIGN LOAD OF THE GAS SYSTEM.
 4) THE GAS DRAWING SHOWS THE DRYER AS GAS BUT IT IS
 SHOWN ON THE PLANS AND ON THE ELECTRICIAN'S LOAD CALCS
 AS ELECTRIC. CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHOW THE LOCATION OF THE GAS WATER HEATERS ON THE
 PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT MANUF. SPECS FOR ALL GAS APPLIANCES /
 EQUIPMENT.APPLIANCES /EQUIPMENT SHALL BE LISTED AND
 LABELED PER 2014 FBC-R SEC. G2404.3.
 7) SUBMIT A GAS PLAN SHOWING THE LOCATION OF THE PE
 PIPE IN RELATION TO THE STRUCTURE. PE PIPE CAN ONLY BE
 USED OUTSIDE UNDERGROUND. 2014 FBC-R SEC.G2415.17.1.
 8) SHOW THE LOCATION OF ALL THE MP
 REGULATORS.REGULATORS SHALL COMPLY WITH 2014 FBC-R SEC.
 G2421.2 (4) [ACCESSIBLE & VENTED TO EXTERIOR], G 2421.2
 (5) (6) [SUPPLIED WITH TEE FITTING FOR MEASURING
 INSTRUMENT & SEDIMENT TRAP.]
 9) SUBMIT MANUF. SPECS FOR THE MP REGULATORS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 10) THE SIZING TABLE SUBMITTED FOR THE PE PIPE IS FROM
 AN OUTDATED CODE STANDARD. THERE HAVE BEEN 2 CODE CYLE
 CHANGES SINCE 2007. SUBMIT COPIES OR REFERNCE THE
 CORRECT AND UPDATED SIZING TABLES USED FOR THE GAS
 DESIGN. WPB AMEND. TO FBC SEC. 107.2.1.
 11) SHOW THE CORRESPONDING EHD FOR THE CSST PIPE. THE
 DIFFERENT EHD NUMBER CARRIES DIFFERNT BTU LOADS.
 12) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE
 APPLIANCES. 2014 FBC-R SEC. G2407.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  