2015-10-01 18:34:511ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRIC
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE LOAD
 CALCULALTIONS, RISER DIAGRAM AND PANEL SCHEDULE ARE
 MISSING THIS.
  
 2) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL SPACE EXCEED 6' FROM AN OUTLET IN
 THE FAMILY ROOM AND MASTER BEDROOM.
  
 3) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2
 FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE.ALSO THE KITCHEN COUNTER TOP APPEARS TO BE
 MISSING A RECEPTACLE OUTLET.
  
 4) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 5) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI
 PROTECTED.
  
 6) NEC 210.52 (E)(1) - AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED
 NOT MORE THAN 6.5 FT. ABOVE GRADE SHALL BE INSTALLED AT
 THE FRONT AND BACK OF THE DWELLING. RECEPTACLE IS
 REQUIRED AT FRONT.
  
 7) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 8) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE
 BONDED.
  
 9) SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED
 FOR THE GENERATOR.
  
  
  