| Date |
Text |
| 2015-10-01 18:34:51 | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY ELECTRIC |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. THE LOAD |
| | CALCULALTIONS, RISER DIAGRAM AND PANEL SCHEDULE ARE |
| | MISSING THIS. |
| | |
| | 2) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME |
| | POINTS ALONG THE WALL SPACE EXCEED 6' FROM AN OUTLET IN |
| | THE FAMILY ROOM AND MASTER BEDROOM. |
| | |
| | 3) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER |
| | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2 |
| | FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN |
| | THAT SPACE.ALSO THE KITCHEN COUNTER TOP APPEARS TO BE |
| | MISSING A RECEPTACLE OUTLET. |
| | |
| | 4) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| | REQUIRED. |
| | |
| | 5) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI |
| | PROTECTED. |
| | |
| | 6) NEC 210.52 (E)(1) - AT LEAST ONE RECEPTACLE OUTLET |
| | ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED |
| | NOT MORE THAN 6.5 FT. ABOVE GRADE SHALL BE INSTALLED AT |
| | THE FRONT AND BACK OF THE DWELLING. RECEPTACLE IS |
| | REQUIRED AT FRONT. |
| | |
| | 7) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL |
| | BE PROVIDED. |
| | |
| | 8) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE |
| | BONDED. |
| | |
| | 9) SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED |
| | FOR THE GENERATOR. |
| | |
| | |
| | |