| 2015-08-28 13:41:45 | 1ST REVIEW: FBC 2014 5TH ED. |
| | |
| | PLEASE PROVIDE SOME KIND OF PLAN AND/OR SCHEDULE FOR |
| | DOOR AAND WINDOW REPLACEMENTS. PROVIDE TYPICALLY |
| | REQUIRED INFOMATION SUCH AS SIZE TYPE OF WINDOW/DOOR, |
| | EXISTING VS PROPOSED CONDITION OPENING LOCATION AND |
| | DESIGN PRESSURES PLANNED EGRESS TO DEMONSTRATE CODE |
| | COMPLIANCE. |
| | |
| | NOTE PER FBC - R301.2.1.2 PROTECTION OF OPENINGS. |
| | WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS |
| | REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM |
| | WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR |
| | WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE |
| | LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12 |
| | OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN. |
| | GARAGE DOOR GLAZED OPENING PROTECTION FOR WINDBORNE |
| | DEBRIS SHALL MEET THE REQUIREMENTS OF AN APPROVED |
| | IMPACT RESISTING STANDARD OR ANSI/DASMA 115. |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | |