| Date |
Text |
| 2015-09-21 13:22:47 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15080380 |
| | ADD: 801 S. OLIVE SUITE # 1409 |
| | CONT: ANDERSON CONSTRUCTION GROUP, LLC |
| | TEL: (561)255-5464 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. SEPT. 21/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) SHEET A2.1; |
| | |
| | 2A) 2ND REQUEST. THE RESPONSE INDICATES SEE UPPER RIGHT |
| | HAND CORNER OF THE SHEET, THE RESPONSE ALSO INDICATES |
| | THEY ARE FILLING IN A RECESS IN A EXISTING FIRE RATED |
| | WALL OUR WORK DOES NOT HAVE TO BE FIRE RATED. IF THE |
| | WALL IS A FIRE RATED WALL THEN YES IT NEEDS A ASSEMBLY |
| | NUMBER, EITHER A UL LISTING OR GYPSUM ASSOCIATION |
| | NUMBER FOR A FIRE RATING FOR THE WALL. |
| | IS THE WALL YOU ARE WORKING ON S METAL STUD WALL AND |
| | THEN THE FIRE RATED WALL BEHIND IT? IF SO PROVIDE THE |
| | DETAIL AS SUCH. |
| | |
| | SHOWS A FIRE RATED WALL BEING FILLED IN, THERE IS NO |
| | INFORMATION AS TO WHAT FRAMING MEMBERS ARE TO BE USED |
| | FOR THE INSTALATION OR FOR THE TYPE OF MATERIAL FOR A 1 |
| | HOUR FIRE RATED ASSEMBLY. 2014 FBC-B 708.3 |
| | FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL HAVE A |
| | FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR. |
| | |
| | 2B) THE FIRE RATED WALL WILL HAVE PENETRATIONS THROUGH |
| | THE DRYWALL, THERE HAS BEEN NO DETAILS SHOWING CODE |
| | COMPLIANCE FOR 2014 FBC-B 708.7 PENETRATIONS. |
| | PENETRATIONS OF FIRE PARTITIONS SHALL COMPLY WITH |
| | SECTION 714. |
| | 714.3 FIRE-RESISTANCE-RATED WALLS. |
| | PENETRATIONS INTO OR THROUGH FIRE WALLS, FIRE BARRIERS, |
| | SMOKE BARRIER WALLS AND FIRE PARTITIONS SHALL COMPLY |
| | WITH SECTIONS 714.3.1 THROUGH 714.3.3. PENETRATIONS IN |
| | SMOKE BARRIER WALLS SHALL ALSO COMPLY WITH SECTION |
| | 714.5. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |