| Plan Review Notes For Permit 15080380 |
| Permit Number |
15080380 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-18 03:57:25 | 1) SUBMIT A FLOOR PLAN FOR THE ENTIRE UNIT SHOWING ALL | | | THE BATHROOMS /.WPB AMEND. TO FBC SEC.107.3.5.1. | | | 2) SUBMIT FIRE SAFING DETAILS FOR ANY PIPING THAT | | | PENETRATES A FIRE RATED PARTITION OF SMOKE | | | PARTITION.COMPLY WITH 2014 FBC SEC. 714. | | | 3) SHT.A-1.0 - THE PLANS REFER TO THE 2010 FBC AND IN | | | GENERAL NOTE #9, THE 2007/2009 CODES ARE REFERENCED. | | | DELETE THESE REFERENCES AND INSERT THE 2014 FBC FAMILY | | | OF CODES. | | | 4) THE PLANS LIST THE OCCUPANCY TYPE OF THIS STRUCTURE | | | AS AN R-3 WHEN IT IS CLEARLY AN R-2 OCCUPANCY.CHANGE | | | THE OCCUPANCY TYPE TO READ R-2. | | | 5) THE PLANS ARE VAGUE AS TO THE SCOPE OF PLUMBING WORK | | | TO BE DONE. IS THE WATER HEATER BEING REPLACED? | | | IDENTIFY IT ON THE PLANS.IDENTIFY ON THE PLANS WHAT | | | EXACTLY IS BEING REPLACED AND WHAT IS EXISTING TO | | | REMAIN. | | | 6) SHT A2.1.-DETAIL #4 - THERE IS A NOTE STATING "NEW | | | WASTE LINE TO EXISTING WASTE STACK" BUT THERE IS NO | | | PIPING SHOWN. CLARIFY. | | | 7) INDICATE ON THE PLANS IF ANY WORK IS TO BE DONE IN | | | THE OTHER BATHROOM. WPB AMEND, TO FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|