| 2015-08-25 07:02:21 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:15080378 |
| | ADD: 777 S. FLAGLER DR. SUITE # 1001E |
| | CONT: BUTLER |
| | TEL: (561)832-9700 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W |
| | * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | |
| | 2014EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. AUGUST 25/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-2.2 ROOM 1006 ADAPTABLE: PLEASE REVIEW THE |
| | 2014 FL ACCESSIBLITY CODE RESTROOMS IN PRIVATE OFFICES |
| | AND WHEN THE EXCEPTION CAN BE APPLIED. THIS CODE IS |
| | CODE ARTICLE SPECIFIC. NOTE SECTION 603 .2.3 DOOR SWING |
| | EXCEPTION # 1 IS SPECIFIC TO TOLIET ROOMS WITHIN |
| | PRIVATE OFFICES, THE DOOR CAN SWING INTO RESTROOMS IN |
| | PRIVATE OFFICE. |
| | |
| | 1A) THE CODE IS ALSO SPECIFIC TO THE REQUIRED OVERLAP |
| | IN 604.3.2. THE CODE DOES NOT GIVE ANY EXCEPTIONS. |
| | PLEASE NOTE THE CODE DOES ALLOW FOR |
| | THE TOLIET SEAT HEIGHT NOT NEEDING TO BE 17- TO 19 |
| | INCHES WITH THE EXCEPTION TOLIET ROOMS IN PRIVATE |
| | OFFICES 604.4. |
| | |
| | 1B) THE CODE DOES ALLOW FOR NOT INSTALLING GRAB BARS IN |
| | A PRIVATE OFFICE BUT THE REINFORCEMENT THAT IS REQUIRED |
| | BY 604.5 DOES NEED TO BE INSTALLED, PLEASE PROVIDE A |
| | DETAIL SHOWING CODE COMPLIANCE WITH 604.5 & 609.8 |
| | STRUCTURAL STRENGTH OF 250 LBS WHEN APPLIED AT ANY |
| | POINT OF THE GRAB BAR. |
| | |
| | 2) SHEET M2.2 INDICATES THE USE OF A WALL MOUNTED MIAMI |
| | TECH WIND RATED CONDENSING UNIT BRAKET AND STAND. |
| | PLEASE PROVIDE A PRODUCT APPROVAL OR ENGINEERING FOR A |
| | SITE SPECIFIC USE. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 3) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |