| Notes |
| Date |
Text |
| 2015-09-09 18:32:36 | 1. ELECTRICAL NOTE 1 HAS THE CODE REFERENCES MIXED UP. | | | NATIONAL ELECTRICAL CODE (NEC) ARTICLE 760, IT SHALL | | | ALSO ADDRESS NFPA 72. NFPA 70 IS THE SAME AS THE NEC. | | | 2. PER FBC-907 YOU SHALL PROVIDE YOUR SCOPE OF WORK ON | | | THE DRAWINGS, AND CLEARLY DEFINE THE WORK. | | | 3. PER FBC 907 YOU SHALL LABEL AND/OR IDENTIFY EVERY | | | ROOM AS TO ITS INTENDED USE. | | | 4. COPPER TAN IS LACKING NOTIFICATION APPLIANCES. | | | 5. CORRECT THE RISER DIAGRAM TO INCLUDE THE ADDED | | | NOTIFICATION APPLIANCES. | | | 6. UPDATE ALL YOUR CALCS TO INCLUDE THE ADDITIONAL | | | DEVICES. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | | | | PS: IF AT ALL POSSIBLE, PLEASE CONSIDER FILING | | | ELECTRONICALLY IN THE FUTURE. IT IS NOT ONLY BETTER ON | | | THE ENVIRONMENT, BUT USUALLY A QUICKER TURN AROUND. | | | |
|