2015-08-28 11:59:08IN THE FUTURE, FOR A QUICKER TURN AROUND TIME, PLEASE
 CONSIDER FILING ELECTRONICALLY. IT IS NOT ONLY BETTER
 FOR OUR ENVIRONMENT, BUT EASIER TO HANDLE AND STORE THE
 DOCUMENTS.
  
 PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. FBC 107.2.1.4 BLDG. PLANS SHALL BE DRAWN TO A
 MINIMUM OF 1/8" SCALE, AND SHALL INCLUDE A DETAILED
 SCOPE OF WORK. FURTHER DEFINE YOUR SCOPE ON THE PERMIT
 APPLICATION AS WELL.
 2. YOUR DEVICE COUNT ON THE SUBMITTED RISER DIAGRAM
 DOES NOT MATCH THE DEVICE COUNT ON THE LEGEND.
 3. THE SUBMITTED RISER DIAGRAM DOES NOT MATCH THE
 DEVICE COUNT ON THE FLOOR PLAN
 4. THE DEVICE LEGEND AND CALCULATION BOXES CALL FOR A
 DIFFERENT POWER SUPPLY THAN THE PROVIDED CUT SHEET.
 5. PROVIDE A CUT SHEET FOR THE CEILING DEVICES.
 6. THE PLANS SHALL INCLUDE THE RESPECTIVE CODE BY WHICH
 THE SYSTEM WAS DESIGNED. (NFPA 70, (NEC) 2011, NFPA 72
 2012)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
  