| Plan Review Notes For Permit 15080340 |
| Permit Number |
15080340 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-12 17:43:28 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRODUCT APPROVALS FOR THE JAMES HARDIE | | | FIBER-CEMENT LAP SIDING (NOA NO.15-0122.03) ARE | | | REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD, RICHARD BOYETTE. FBC 107.3.4.1 | | | | | | 2) THE PRODUCT APPROVALS FOR THE JAMES HARDIE | | | FIBER-CEMENT LAP SIDING (NOA NO.15-0122.03) REQUIRES | | | 5/8" THICK / 5 PLY APA RATED PLYWOOD SHEATHING AND THE | | | APPROVED PLANS SPECIFY 1/2" PLYWOOD SHEATHING. SUBMIT | | | REVISED PLANS. | | | | | | | | | |
|