| Plan Review Notes For Permit 15080324 |
| Permit Number |
15080324 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-07 10:07:44 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15080324 | | | 10/7/15 | | | | | | 1) THE TRANE 6-TON SYSTEM HAS AN AIRFLOW CAPACITY THAT | | | WILL EXCEED 2000 CFM'S- PLEASE REFER TO SECTION 606.2.1 | | | AND PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR | | | SYSTEM. INDICATE CONTROL OPERATION AND SUPERVISORY | | | DETAILS FOR THE DEVICE- SEE SECTIONS 606.4 AND 606.4.1. | | | 2) SHEET M1.1: PLEASE RELOCATE THE RETURN AIR GRILLS | | | FOR AHU-1 SHOWN ON THE PLAN IN CLOSE PROXIMITY OF THE | | | EXHAUST HOOD- SEE TABLE 403.3 (OCCUPANCY | | | CLASSIFICATION-KITCHENS) FOOTNOTE B. | | | 3) M1.2: REMOVE THE WINDLOAD DETAILS FOR THE 3-TON CU, | | | AND REPLACE WITH DETAILS FOR THE 6-TON UNIT. SEE | | | COMMENT #3 FROM THE 1ST REVIEW: MIAMI TECH AC STAND | | | NOA- AS PREVIOUSLY REQUESTED PLEASE CIRCLE, HIGHLIGHT, | | | OR OTHERWISE MARK ALL APPLICABLE DETAILS, NOTES, DESIGN | | | PRESSURES, TABLES, ETC. SHOWN ON THE DOC PERTAINING TO | | | THE PROPOSED INSTALLATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|