| Plan Review Notes For Permit 15080324 |
| Permit Number |
15080324 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-26 15:24:54 | 1) WALLS WITHIN TWO FEET OF WATER CLOSETS SHALL HAVE A | | | SMOOTH, HARD NONABSORBANT SURFACE TO A HEIGHT OF 4 | | | FEET.THE PLANS NOTE "WASHABLE FLAT PAINT". MY CONCERN | | | IS OF THE DURABILITY OF THE PAINT TO WITHSTAND THE | | | ENVIRONMENT TO WHICH IT WILL BE SUBJECTED. | | | 2) SHT.P0.1 HAS GREASE TRAP CALCULATIONS FOR A 750 | | | GALLON GREASE TRAP YET SHT. P0.2 REFERS TO A 1250 | | | GALLON GREASE TRAP. CLARIFY. | | | 3) SHT.P0.2 - THE REFERENCED TABLE FOR THE 2 PSI GAS | | | SYSTEM IS INCORRECT. THE TABLE NUMBER IN THE 2014 | | | FBC-FUEL GAS IS 402.4 (5). PLEASE REVISE. | | | 4) THE SANITARY LINE FOR THE FLOOR SINKS SHALL BE | | | VENTED.FBC-PLUMBING SEC.901.2. | | | 5) SUBMIT A SLAB REPAIR DETAIL FOR THE REPAIR OF ANY | | | POTION OF THE EXISTING SLAB THAT WILL HAVE TO BE CUT TO | | | ACCOMMODATE THE REROUTING OF ANY PLUMBING. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 6) PROVIDE THE KITCHEN DRAWINGS NOTED ON THE COVER | | | SHEET FOR REVIEW.WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|