| 2015-08-17 11:38:05 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15080324 | | | 8/17/15 | | | | | | 1) SHEET M1.1: PLEASE PROVIDE A NOTE INDICATING THAT | | | THE WALK-IN COOLER AND FREEZER WILL BE UNDER A SEPARATE | | | PERMIT. | | | 2) PLEASE PROVIDE THE KITCHEN PLANS SHOWN IN THE INDEX | | | AS K0.1- K5.2 | | | 3) REFER TO SECTION 301.15 FBC-14 MECHANICAL: WIND | | | RESISTANCE. | | | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE | | | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO | | | RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH | | | THE FLORIDA BUILDING CODE, BUILDING. | | | PLEASE PROVIDE THE DESIGN PRESSURES ON THE PLANS AND | | | SUBMIT TWO COPIES OF THE NOA #13-1017.09 FOR THE | | | MIAMI-TECH ROOF STAND WITH ALL APPLICABLE INSTALLATION | | | DETAILS, NOTES, SCHEDULES, AND TABLES CIRCLED, | | | HIGHLIGHTED, OR OTHERWISE MARKED TO CORRELATE WITH THE | | | INSTALLATION DESIGN SHOWN ON THE PLANS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|