2015-08-28 07:27:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080324
 ADD: 7800 OKEECHOBEE BLVD SUITE # A18
 CONT: THE EVERGLADES GROUP
 TEL: (561)912-0400
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2014 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRIDAY OCT. 02/2015
 ACTION: DENIED
  
 1A) 2014 EXISITNG BUILDING CODE 806.1 A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY. THE DOOR TO RESTROOM 106 IS NOT
 ACCESSIBLE WITH THE WIDTH OF THE CORRIDOR AT 51 INCHES
 WIDE. 202.4.1 DISPROPORTIONATE COST UP TO 20 % OF THE
 CONTRACT VALUE OR $51,412.00 DOLLORS IN ACCESSIBLE
 UPGRADES. THERE IS AN ACCESSIBLE ENTRANCE WITH BOTH
 FRONT DOORS BEING ON AN ACCESSIBLE ROUTE. THE NEXT AREA
 IS AN ACCESSIBLE ROUTE TO ALTERED AREAS, AND THEN
 RESTROOMS THE DOOR # 106 YOU CAN NOT GET BY IT. SHEET
 A-905 DETAIL (E) SHOWS A MINIMUM OF 54 INCHES TO WHEEL
 BY THAT DOOR. PLEASE SHOW HOW COMPLIANCE WITH 2014
 ACCESS. CODE FIGURE 404.2.4.1(E) WILL BE ACHIEVED.
  
 NOTE A SIMPLE FIX FOR THIS DOOR AS WELL AS THE MENS
 RESTROOM DOOR IS THE USE OF A INSWING DOOR. 2014
 ACCESS. CODE 603.2.3 DOOR SWING EXCEPTION # 2. WHERE
 THE TOILET ROOM OR BATHING ROOM IS FOR INDIVIDUAL USE
 AND A CLEAR FLOOR SPACE COMPLYING WITH 305.3 IS
 PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE DOOR
 SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE CLEAR
 FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE
  
 1A) 1ST REVIEW COMMENT. SHEET A-120 & A-250 THE LIFE
 SAFETY PLAN INDICATES THE CORRIDOR INFRONT OF THE
 RESTROOMS TO BE 4'-3" OR 51 INCHES WIDE. PLEASE COMPLY
 WITH SECTION 1005.7.1 DOOR SWING. DOORS, WHEN FULLY
 OPENED, SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN 7 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT
 REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
 36INCHES + 22 INCHES(1/2 0F 44 INCHES)= 58 INCHES
 MINIMUM.
  
 1B) COMPLIED.
  
 1C) COMPLIED, NOT A ACCESSIBLE EXIT
  
 2) COMPLIED.
  
 3) RESPONSE INDICATES RESTROOMS ARE EXISITNG AND THE
 EXISITNG DRAWING INDICATE MOISTURE RESISTANT BOARD IN
 THESE AREAS. PLEASE SEE THERE APPEARS TO BE A
 DISCREPANCY IN THE PLANS. THE COVERSHEET UNDER THE
 SCOPE OF WORK; COMPLETE RENOVATION OF DINING ROOM,
 KITCHEN AND RESTROOM VERSES SHEET A 250 AREA NOT IN
 SCOPE OF WORK GRAY SHADED AREA. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  