| 2015-08-26 15:01:32 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15080312 |
| | 8/26/15 |
| | |
| | 1) SIZING CALCULATIONS REQUIRED FOR WSHP-1. REFER TO |
| | C403.2.1 FBC-14 ENERGY CONSERVATION- CALCULATION OF |
| | HEATING AND COOLING LOADS. |
| | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE |
| | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR |
| | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE |
| | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT |
| | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE |
| | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE |
| | SIZING CALCULATION SHALL BE SUBMITTED WITH THE |
| | APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND |
| | COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD |
| | REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY |
| | SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE |
| | WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK. |
| | ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN |
| | APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE |
| | DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. |
| | 2) A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR |
| | SYSTEM OF WSHP-1- REFER TO SECTION 606.2.1 FBC-14 |
| | MECHANICAL. RETURN AIR SYSTEMS. |
| | SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR |
| | SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM |
| | (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF |
| | ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR |
| | CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND |
| | APPLIANCES. |
| | 3) PROVIDE A NARRATIVE DESCRIPTION AND DIAGRAM |
| | DETAILING THE SMOKE DETECTOR CONTROLS OPERATION AND |
| | SUPERVISION- SECTIONS 606.4 & 606.4.1. |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SMOKE |
| | DETECTOR AND FIRE DAMPER. THE SUBMITTALS SHALL BRE |
| | REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF |
| | RECORD. |
| | 5) SEE SECTION 809.2 FBC-14 EXISITNG BUILDING CODE: |
| | ALTERED EXISTING SYSTEMS. |
| | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL |
| | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR |
| | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER |
| | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR |
| | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION |
| | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF |
| | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY |
| | PROCEDURE OF ASHRAE 62. PLEASE PROVIDE CALCULATIONS AND |
| | A VENTILATION SCHEDULE TO VERIFY COMPLIANCE. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |