2015-12-29 09:18:47BUILDING PLAN REVIEW
 W. P. B. PERMIT:15080304
 ADD: 2100 45TH ST.
 CONT: TBD/ TO BE DETERMINED
 TEL: (???)???-????
 E-MAIL:????????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 4TH REVIEW
 DATE: TUES. DEC. 29/ 2015
 ACTION: DENIED
  
  
 1) 4TH REQUEST. THE UNDERGROUND STORAGE TANKS AND
 INSTALATION OF UNDERGROUND PIPING AND 6 NEW DISPENSERS
 WILL REQUIRE A PCP CONTRATOR SIGNED ON TO VERIFY
 LICENSURE BEFORE PERMIT ISSUANCE. FL. S. 489.105(P)
 ALSO SEE F. S. 376.303. UNLESS THE PCP CONTRACTOR HOLDS
 A SECOND LICENSE FOR THE CANOPY, ANOTHER CONTRACTOR
 WILL BE REQUIRED TO SIGN ONTO THE PERMIT APPLICATION.
  
 2-7) COMPLIED.
  
 8 ) 4TH REQUEST .BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved