2015-11-10 15:56:59BUILDING PLAN REVIEW
 W. P. B. PERMIT:15080304
 ADD: 2100 45TH ST.
 CONT: TBD/ TO BE DETERMINED
 TEL: (???)???-????
 E-MAIL:????????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2ND REVIEW
 DATE: FRI. OCT. 16/ 2015
 ACTION: DENIED
  
 ) NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 1)3RD REQUEST. THE UNDERGROUND STORAGE TANKS AND
 INSTALATION OF UNDERGROUND PIPING AND 6 NEW DISPENSERS
 WILL REQUIRE A PCP CONTRATOR SIGNED ON TO VERIFY
 LICENSURE BEFORE PERMIT ISSUANCE. FL. S. 489.105(P)
 ALSO SEE F. S. 376.303. UNLESS THE PCP CONTRACTOR HOLDS
 A SECOND LICENSE FOR THE CANOPY, ANOTHER CONTRACTOR
 WILL BE REQUIRED TO SIGN ONTO THE PERMIT APPLICATION.
  
 2) COMPLIED. NOTE 2 PERMITS WERE APPIED FOR 15080304
 UNDERGOUND STORAGE TANKS AND 15080306 A 3,096 SQ. FT
 CANOPY. NOTE ONLY 2 SETS OF PLANS WERE SUBMITTED.
 PLEASE NOTE ONLY SHEET G8 SHOWS ELEVATION OF THE
 CANOPY, NO DETAILS, STURTURAL SHEETS NOR WIND DESIGN
 WAS INCLUDED. 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. IF THE DETAILS FOR TTHE CANOPY ARE TO BE
 INCORPORATED INTO ONE SET OF PLANS, THEN 4 SETS OF
 PLANS WILL BE REQUIRED. 2 SETS FOR EACH PERMIT.
  
 3-6) COMPLIED.
  
 7) 3RD REQUEST. ONLY (1) SOILS REPORT SUBMITED, (2 )
 WILL BE REQUIRED FOR THE UNDERGROUND TANKS AND (2) FOR
 THE CANOPY. THE SOILS REPORT INDICATES THERE TO BE
 UNDER LAYING ORGANIC SOILS. THE SOILS REPORT IS
 SUGESTIONSAND ALTERNATIVES IN DEALING WITH THIS MATTER.
 THE DESIGNER OF RECORD HAS NOT RESPONDED AS TO HOW THE
 ORGANIC SOILS ARE TO BE DELT WITH.
  
 THE (2) ISSUE IS THAT GROUND WATER WILL BE PRESENT
 AROUND 7 FEET BELOW GRADE, PLEASE PROVIDE HOW THE
 GROUND WATER WILL BE LOWERED TO BE ABLE TO WORK AT THE
 REQUIRED DEEPER ELEVATION FROM GRADE.
  
 SHEET G1 INDICATES THE TANKS TO BE 10 FT. DIAMETER AND
 APPROXIMATELY 15 FEET BELOW GRADE. TO DATE THERE HAS
 BEEN NO SOILS REPORT SUBMITTED AS TO THE WATER TABLE
 LEVEL, AND HOW OR IF DEWATERING WILL BE REQUIRED AT
 THIS SITE SINCE THERE IS A CANAL JUST WEST OF THIS
 PROPERTY.
 2014 FBC-B 1803.3 BASIS OF SOILS INVESTIGATION.
  
 8 ) 3RD REQUEST) .BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  