| 2015-10-16 12:21:29 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:15080304 |
| | ADD: 2100 45TH ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: (???)???-???? |
| | E-MAIL:???????????????? |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 2ND REVIEW |
| | DATE: FRI. OCT. 16/ 2015 |
| | ACTION: DENIED |
| | |
| | ) NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | 1)2ND REQUEST. THE UNDERGROUND STORAGE TANKS AND |
| | INSTALATION OF UNDERGROUND PIPING AND 6 NEW DISPENSERS |
| | WILL REQUIRE A PCP CONTRATOR SIGNED ON TO VERIFY |
| | LICENSURE BEFORE PERMIT ISSUANCE. FL. S. 489.105(P) |
| | ALSO SEE F. S. 376.303. UNLESS THE PCP CONTRACTOR HOLDS |
| | A SECOND LICENSE FOR THE CANOPY, ANOTHER CONTRACTOR |
| | WILL BE REQUIRED TO SIGN ONTO THE PERMIT APPLICATION. |
| | |
| | 2) COMPLIED. NOTE 2 PERMITS WERE APPIED FOR 15080304 |
| | UNDERGOUND STORAGE TANKS AND 15080306 A 3,096 SQ. FT |
| | CANOPY. NOTE ONLY 2 SETS OF PLANS WERE SUBMITTED. |
| | PLEASE NOTE ONLY SHEET G8 SHOWS ELEVATION OF THE |
| | CANOPY, NO DETAILS, STURTURAL SHEETS NOR WIND DESIGN |
| | WAS INCLUDED. 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. IF THE DETAILS FOR TTHE CANOPY ARE TO BE |
| | INCORPORATED INTO ONE SET OF PLANS, THEN 4 SETS OF |
| | PLANS WILL BE REQUIRED. 2 SETS FOR EACH PERMIT. |
| | |
| | 3) 2ND REQUEST. RESPONSE INDICATES THE PLANS WERE |
| | SUBMITTED TO DERM ELECTRONICALLY PLEASE SHOW APPROVAL. |
| | THE UNDERGROUND STORAGE TANKS WILL NEED TO BE REVIEWED |
| | BY P. B. C. DEPARTMENT OF ENVIROMENTAL RESOURSES |
| | MANAGEMENT FOR REVIEW AND APPROVAL, PLANS STAMPED BY |
| | THE AGENCY AND RETURNED FOR REVIEW BY THE CITY BUILDING |
| | DEPARTMENT. 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS.12. ENVIROMENTAL REQUIREMENTS. |
| | |
| | 4) COMPLIED. THE LISTED FAMILY OF CODES LIST THE 2010 |
| | FBC AS THE CODE THE DOCUMENTS WERE DESIGNED TOO. PLEASE |
| | UPDATE THE PLANS TO THE 2014 5TH EDITION OF THE FLORIDA |
| | BUILDING CODE, ADOPTED STATWIDE ON JUNE 30/ 2015. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) COMPLIED |
| | |
| | 7) 2ND REQUEST. ONLY (1) SOILS REPORT SUBMITED, (2 ) |
| | WILL BE REQUIRED FOR THE UNDERGROUND TANKS AND (2) FOR |
| | THE CANOPY. THE SOILS REPORT INDICATES THERE TO BE |
| | UNDER LAYING ORGANIC SOILS. THE SOILS REPORT IS |
| | SUGESTIONSAND ALTERNATIVES IN DEALING WITH THIS MATTER. |
| | THE DESIGNER OF RECORD HAS NOT RESPONDED AS TO HOW THE |
| | ORGANIC SOILS ARE TO BE DELT WITH. |
| | |
| | THE (2) ISSUE IS THAT GROUND WATER WILL BE PRESENT |
| | AROUND 7 FEET BELOW GRADE, PLEASE PROVIDE HOW THE |
| | GROUND WATER WILL BE LOWERED TO BE ABLE TO WORK AT THE |
| | REQUIRED DEEPER ELEVATION FROM GRADE. |
| | |
| | SHEET G1 INDICATES THE TANKS TO BE 10 FT. DIAMETER AND |
| | APPROXIMATELY 15 FEET BELOW GRADE. TO DATE THERE HAS |
| | BEEN NO SOILS REPORT SUBMITTED AS TO THE WATER TABLE |
| | LEVEL, AND HOW OR IF DEWATERING WILL BE REQUIRED AT |
| | THIS SITE SINCE THERE IS A CANAL JUST WEST OF THIS |
| | PROPERTY. |
| | 2014 FBC-B 1803.3 BASIS OF SOILS INVESTIGATION. |
| | |
| | 8 ) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |