Plan Review Notes
Plan Review Notes For Permit 15080304
Permit Number 15080304
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-24 08:21:54BUILDING PLAN REVIEW
 W. P. B. PERMIT:15080304
 ADD: 2100 45TH ST.
 CONT: TBD/ TO BE DETERMINED
 TEL: (???)???-????
 E-MAIL:????????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 1ST REVIEW
 DATE: MON. AUGUST 24/ 2015
 ACTION: DENIED
  
 1) THE UNDERGROUND STORAGE TANKS AND INSTALATION OF
 UNDERGROUND PIPING AND 6 NEW DISPENSERS WILL REQUIRE A
 PCP CONTRATOR SIGNED ON TO VERIFY LICENSURE BEFORE
 PERMIT ISSUANCE. FL. S. 489.105(P) ALSO SEE F. S.
 376.303. UNLESS THE PCP CONTRACTOR HOLDS A SECOND
 LICENSE FOR THE CANOPY, ANOTHER CONTRACTOR WILL BE
 REQUIRED TO SIGN ONTO THE PERMIT APPLICATION.
  
 2) NOTE 2 PERMITS WERE APPIED FOR 15080304 UNDERGOUND
 STORAGE TANKS AND 15080306 A 3,096 SQ. FT CANOPY. NOTE
 ONLY 2 SETS OF PLANS WERE SUBMITTED. PLEASE NOTE ONLY
 SHEET G8 SHOWS ELEVATION OF THE CANOPY, NO DETAILS,
 STURTURAL SHEETS NOR WIND DESIGN WAS INCLUDED. 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. IF THE
 DETAILS FOR TTHE CANOPY ARE TO BE INCORPORATED INTO ONE
 SET OF PLANS, THEN 4 SETS OF PLANS WILL BE REQUIRED. 2
 SETS FOR EACH PERMIT.
  
 3) THE UNDERGROUND STORAGE TANKS WILL NEED TO BE
 REVIEWED BY P. B. C. DEPARTMENT OF ENVIROMENTAL
 RESOURSES MANAGEMENT FOR REVIEW AND APPROVAL, PLANS
 STAMPED BY THE AGENCY AND RETURNED FOR REVIEW BY THE
 CITY BUILDING DEPARTMENT. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.12. ENVIROMENTAL REQUIREMENTS.
  
 4) THE LISTED FAMILY OF CODES LIST THE 2010 FBC AS THE
 CODE THE DOCUMENTS WERE DESIGNED TOO. PLEASE UPDATE THE
 PLANS TO THE 2014 5TH EDITION OF THE FLORIDA BUILDING
 CODE, ADOPTED STATWIDE ON JUNE 30/ 2015.
  
 5) SHEET G1 PROVIDES THE DEAD WEIGHT DESIGN FOR THE USE
 OF THE DEAD MEN FOR EACH TANK, THE CENTER DEAD MAN CAN
 NOT BE SHARED AS DEPICTED. THE DESIGN OF THE DEADMAN IS
 18 INCHES WIDE, 8.75 INCHES IN HEIGHT AND 36 FEET LONG.
 PLEASE PROVIDE IF THIS IS A PRECAST UNIT OR IS THIS
 POURED IN PLACE? IF PRE-CAST IS THERE STEEL REBAR
 ENCASED ? IF POURED IS THERE TO BE STEEL
 RE-INFORCEMENT? IS THERE ANCHOR PROTRUDING FROM THE
 DEADMEN? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) SHEET G3 NOTE # 4 INDICATES THE USE OF MOH STRAP
 ANCHOR SYSTEM TO BE SUPPLIED BY THE TANK MANUFACTURER
 AND THE DEAD MEN ARE TO BE PLACED PER THE MANUFACTURERS
 INSTALLATION INSTRUCTION, PLEASE SUBMIT BOTH THE MOH
 STRAP ANCHOR SYSTEM AS WELL AS THE DEAD MEN INSTALATION
 INSTRUCTIONS. THE MOH SYSTEM WILL NEED TO INDICATE THE
 TYPE OF STRAPS, CENTER TO CENTER PLACEMENT AND HOW THEY
 ARE ATTACHED TO THE DEADMEN. 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. .12. ENVIROMENTAL
 REQUIREMENTS.
  
 7) SHEET G1 INDICATES THE TANKS TO BE 10 FT. DIAMETER
 AND APPROXIMATELY 15 FEET BELOW GRADE. TO DATE THERE
 HAS BEEN NO SOILS REPORT SUBMITTED AS TO THE WATER
 TABLE LEVEL, AND HOW OR IF DEWATERING WILL BE REQUIRED
 AT THIS SITE SINCE THERE IS A CANAL JUST WEST OF THIS
 PROPERTY.
 2014 FBC-B 1803.3 BASIS OF SOILS INVESTIGATION.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  