2015-12-17 14:40:33BUILDING PLAN REVIEW
 W. P. B. PERMIT:15080289
 ADD: 1001 OKEECHOBEE BLVD
 CONT: C & I CONSTRUCTION & DESGIN
 TEL: (305)255-6067
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. DEC. 17 / 2014
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 1) PLANS FAIL TO PROVIDE CODE COMPLIANCE WITH THE 2014
 FBC-B 3110.3 VEHICULAR GATES INTENDED FOR AUTOMATION.
 VEHICULAR GATES INTENDED FOR AUTOMATION SHALL BE
 DESIGNED, CONSTRUCTED AND INSTALLED TO COMPLY WITH THE
 REQUIREMENTS OF ASTM F 2200-05. PLEASE PROVIDE THE
 MANUFACTURERS SPEC ON THIS PRODUCT SHOWING CODE
 COMPLIANCE.
  
 2) VEHICULAR GATE OPENERS 2014 FBC-B 3110. VEHICULAR
 GATE OPENERS, WHEN PROVIDED, SHALL BE LISTED IN
 ACCORDANCE WITH UL 325.PLEASE PROVIDE THE MANUFATURERS
 SPEC ON THIS PRODUCT SHOWING CODE COMPLIANCE.
  
 3) THERE IS NO WIND DESIGN CRITERIA NOR HOW THIS
 EQUIPMENT WILL BE ANCHORED TO WITHSTAND THE MOMENT OF
 OVER TURNING FOR THIS WIND BORN DEBRIS REGION? BUILDING
 CATEGORY I WIND ZONE 160 MPH VULT. 3 SECOND GUST
  
 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  