| 2015-10-21 16:32:28 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: |
| | ADD: 1001 OKEECHOBBEE BLVD |
| | CONT: C & I CONSTRUCTION & DESIGN, INC. |
| | TEL: (305)255-6067 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. OCT. 21/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. PLANS FAIL TO PROVIDE CODE COMPLIANCE |
| | WITH THE 2014 FBC-B 3110.3 VEHICULAR GATES INTENDED FOR |
| | AUTOMATION. VEHICULAR GATES INTENDED FOR AUTOMATION |
| | SHALL BE DESIGNED, CONSTRUCTED AND INSTALLED TO COMPLY |
| | WITH THE REQUIREMENTS OF ASTM F 2200-05. PLEASE PROVIDE |
| | THE MANUFACTURERS SPEC ON THIS PRODUCT SHOWING CODE |
| | COMPLIANCE. |
| | |
| | SHEET 1851-06 UNDER THE HEADING OF NOTES. IT IS THE |
| | RESPONSIBILITY OF THE INSTALLER TO VERIFY ALL |
| | INFORMATION CONTAINED HEREIN AS IT RELATES TO THE |
| | ACTUAL SYSTEM DESIGN, SITE CONDITIONS AND CODE |
| | REQUIREMENTS. |
| | |
| | |
| | 2) 2ND REQUEST. VEHICULAR GATE OPENERS 2014 FBC-B 3110. |
| | VEHICULAR GATE OPENERS, WHEN PROVIDED, SHALL BE LISTED |
| | IN ACCORDANCE WITH UL 325. |
| | |
| | SHEET 1851-06 UNDER THE HEADING OF NOTES. IT IS THE |
| | RESPONSIBILITY OF THE INSTALLER TO VERIFY ALL |
| | INFORMATION CONTAINED HEREIN AS IT RELATES TO THE |
| | ACTUAL SYSTEM DESIGN, SITE CONDITIONS AND CODE |
| | REQUIREMENTS. |
| | |
| | |
| | 3) 2ND REQUEST. THE WIND DESIGN PROVIDED ON SHEET |
| | TITLED EQUIPMENT MOUNTING-AMG WEDGE ANCHORS INDICATES |
| | WIND UPLIFT OF 146 MPH. THE PLANS DOES NOT INDICATE IF |
| | THIS WIND SPEED IS VULT OR VASD? FOR STRUCTURES WITH A |
| | RISK CATEGORY I THE WIND SPEED INDICATES ON FIGURE |
| | 1609C RISK CATEGORY I STRUCTURES AND BUILDINGS WE ARE |
| | LOCATED IN A 160 VULT MPH 3 SECOND GUST WIND ZONE. |
| | |
| | PLEASE PROVIDE ADDITIONAL INFORMATION TO INDICATE CODE |
| | COMPLIANCE. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |