2015-10-21 16:32:28BUILDING PLAN REVIEW
 W. P. B. PERMIT:
 ADD: 1001 OKEECHOBBEE BLVD
 CONT: C & I CONSTRUCTION & DESIGN, INC.
 TEL: (305)255-6067
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. OCT. 21/ 2014
 ACTION: DENIED
  
 1) 2ND REQUEST. PLANS FAIL TO PROVIDE CODE COMPLIANCE
 WITH THE 2014 FBC-B 3110.3 VEHICULAR GATES INTENDED FOR
 AUTOMATION. VEHICULAR GATES INTENDED FOR AUTOMATION
 SHALL BE DESIGNED, CONSTRUCTED AND INSTALLED TO COMPLY
 WITH THE REQUIREMENTS OF ASTM F 2200-05. PLEASE PROVIDE
 THE MANUFACTURERS SPEC ON THIS PRODUCT SHOWING CODE
 COMPLIANCE.
  
 SHEET 1851-06 UNDER THE HEADING OF NOTES. IT IS THE
 RESPONSIBILITY OF THE INSTALLER TO VERIFY ALL
 INFORMATION CONTAINED HEREIN AS IT RELATES TO THE
 ACTUAL SYSTEM DESIGN, SITE CONDITIONS AND CODE
 REQUIREMENTS.
  
  
 2) 2ND REQUEST. VEHICULAR GATE OPENERS 2014 FBC-B 3110.
 VEHICULAR GATE OPENERS, WHEN PROVIDED, SHALL BE LISTED
 IN ACCORDANCE WITH UL 325.
  
 SHEET 1851-06 UNDER THE HEADING OF NOTES. IT IS THE
 RESPONSIBILITY OF THE INSTALLER TO VERIFY ALL
 INFORMATION CONTAINED HEREIN AS IT RELATES TO THE
 ACTUAL SYSTEM DESIGN, SITE CONDITIONS AND CODE
 REQUIREMENTS.
  
  
 3) 2ND REQUEST. THE WIND DESIGN PROVIDED ON SHEET
 TITLED EQUIPMENT MOUNTING-AMG WEDGE ANCHORS INDICATES
 WIND UPLIFT OF 146 MPH. THE PLANS DOES NOT INDICATE IF
 THIS WIND SPEED IS VULT OR VASD? FOR STRUCTURES WITH A
 RISK CATEGORY I THE WIND SPEED INDICATES ON FIGURE
 1609C RISK CATEGORY I STRUCTURES AND BUILDINGS WE ARE
 LOCATED IN A 160 VULT MPH 3 SECOND GUST WIND ZONE.
  
 PLEASE PROVIDE ADDITIONAL INFORMATION TO INDICATE CODE
 COMPLIANCE. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  