| Plan Review Notes For Permit 15080289 |
| Permit Number |
15080289 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-17 14:43:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE GATES OR GATE FOUNDATION SHALL NOT ENCROUCH INTO | | | THE EXISTING DRIVE PATHS AS THEY ARE PREVIOUSLY | | | APPROVED FIRE LANES. | | | | | | 2) FIRE LANES ACCESS SHALL BE A MINIMUM OF 20FT. ON THE | | | NORTH DRIVE PATH DIMENSIONS INDICATE 16'10" AND 17'10" | | | RESPECTFULLY. HOWVER, THERE IS AN EXISTING PREVIOUSLY | | | APPROVED ISLAND MEDIUM THAT CAN REMAIN. THE EQUIPMENT | | | MAY BE MOVED INTO THE ISLAND MEDIUM. | | | | | | 3) ON THE SOUTH WEST LOCATION, DRIVE LANES ARE REDUCED | | | TO 13'1" AND ARE NOT APPROVED. FIRE LANES ACCESS SHALL | | | BE A MINIMUM OF 20FT. | | | | | | 4) ON THE SOUTH EAST LOCATION, ONE DRIVE LINE IS | | | REDUCED TO 11' AND THE OTHER SIDE IS NOT INDICATED BUT | | | APPEARS TO BE LESS THAN 11' AND IS NOT APPROVED. FIRE | | | LANES ACCESS SHALL BE A MINIMUM OF 20FT. | | | | | | 5) ANY GATE ACESS SHALL HAVE KNOX KEY SWITCHES FOR 24 | | | EMERGENCY ACCESS. | | | |
|