Plan Review Notes
Plan Review Notes For Permit 15080289
Permit Number 15080289
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-08-17 14:43:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE GATES OR GATE FOUNDATION SHALL NOT ENCROUCH INTO
 THE EXISTING DRIVE PATHS AS THEY ARE PREVIOUSLY
 APPROVED FIRE LANES.
  
 2) FIRE LANES ACCESS SHALL BE A MINIMUM OF 20FT. ON THE
 NORTH DRIVE PATH DIMENSIONS INDICATE 16'10" AND 17'10"
 RESPECTFULLY. HOWVER, THERE IS AN EXISTING PREVIOUSLY
 APPROVED ISLAND MEDIUM THAT CAN REMAIN. THE EQUIPMENT
 MAY BE MOVED INTO THE ISLAND MEDIUM.
  
 3) ON THE SOUTH WEST LOCATION, DRIVE LANES ARE REDUCED
 TO 13'1" AND ARE NOT APPROVED. FIRE LANES ACCESS SHALL
 BE A MINIMUM OF 20FT.
  
 4) ON THE SOUTH EAST LOCATION, ONE DRIVE LINE IS
 REDUCED TO 11' AND THE OTHER SIDE IS NOT INDICATED BUT
 APPEARS TO BE LESS THAN 11' AND IS NOT APPROVED. FIRE
 LANES ACCESS SHALL BE A MINIMUM OF 20FT.
  
 5) ANY GATE ACESS SHALL HAVE KNOX KEY SWITCHES FOR 24
 EMERGENCY ACCESS.
  