| 2015-08-12 08:14:20 | 8/12/2015 |
| | PROJECT: LEEPER DR. |
| | PERMIT#: 15080287 |
| | CODE: 2011 EDITION OF THE NEC, 5TH EDITION OF THE FBC, |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | SECOND REQUEST. |
| | 1) PROVIDE TWO COPIES OF A SITE PLAN AND FLOOR PLAN |
| | INDICATING THE LOCATIONS OF ALL LOW VOLTAGE COMPONENTS |
| | PROPOSED TO BE INSTALLED. WPB AMENDMENTS TO FBC |
| | SECTION107 |
| | THE RESUBMITTAL PROVIDED INCLUDES ONLY ONE FLOOR PLAN |
| | FROM THE LEEPER DR. PROJECT. THERE IS ANOTHER FLOOR |
| | PLAN INCLUDED BUT IT IS FOR A DIFFERENT PROJECT IN A |
| | DIFFERENT MUNICIPALITY. |
| | TWO SETS OF SIGNED PLANS ARE REQUIRED. WPB AMENDMENTS |
| | TO THE FBC 107.3. |
| | THE SCOPE OF WORK ON THE PLAN SUBMITTED DOES NOT MATCH |
| | THE PROPOSED SCOPE OF WORK SUBMITTED WITH THE |
| | APPLICATION. THE FLOOR PLAN THAT WAS SUBMITTED ONLY |
| | SHOWS TWO DATA DROPS. THE PROPOSAL SUBMITTED IS FOR 5 |
| | FLOOR BOXES, 10 DATA DROPS AN EQUIPMENT RACK PATCH |
| | PANEL, FIRE WALL PENETRATIONS, ETC... |
| | |
| | SECOND REQUEST. |
| | 2) PROVIDE TWO COPIES OF THE MANUFACTURER PRODUCT DATA |
| | SHEETS FOR ALL PRODUCTS PROPOSED TO BE INSTALLED |
| | INDICATING COMPLIANCE WITH NEC 110.3 AND ARTICLE 800. |
| | |
| | SECOND REQUEST. |
| | 3) THE APPLICATION IS INCOMPLETE. PROVIDE A COMPLETE |
| | DESCRIPTION OF THE SCOPE OF WORK, AND A COMPLETE |
| | CONTRACTOR LICENSE NUMBER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |