| Date |
Text |
| 2015-10-29 09:22:34 | 1) SUBMIT CALCULATIONS FOR COMBUSTION AIR. 2ND REQUEST. |
| | 2014 FBC-RES. SEC. G2407. |
| | 2) THE TOTAL BTU LOAD I HAVE CALCULATED FOR THIS SYSTEM |
| | BASED ON THE BTU LOAD SHOWN IS 1,103,000 BTU'S. REVISE |
| | TOTAL BTU LOAD ON THE PLAN. |
| | 3) BASED ON THE TOTAL BTU LOAD OF THE LOW PRESSURE |
| | SYSTEM AND THE DISTANCE TO THE MOST REMOTE OUTLET (114 |
| | FT. ) THE GALVANIZED LINE FROM THE REGULATOR SHALL BE A |
| | MINIMUM OF 2 INCHES IN SIZE UP TO THE FIRST TRANSITION |
| | TO CSST PER TABLE G2413.4 (1) OF 2014 FBC-RES. |
| | 4) THE 10 FOOT SECTION OF CSST SHALL BE 2", NOT 1 1/4" |
| | AS SHOWN PER TABLE G 2413.4 (5) OF 2014 FBC-RES. |
| | 5) THE 60 FOOT SECTION OF CSST SHALL BE 2", NOT 1 1/4 " |
| | PER 2014 FBC-RES. GAS TABLE G 2413.4 (5) OF 2014 |
| | FBC-RES. |
| | 6) THE SIZE OF THE CSST TO THE TANKLESS WATER HEATER IN |
| | THE MASTER BATH SHALL BE 1 1/4" PER 2014 FBC-RES. TABLE |
| | G2413.4 (5) AND THE GALVANIZED SHALL BE 1 1/4" PER |
| | TABLE G2413.4 (1). |
| | 7) THE SIZE OF THE GALVANIZED LINE TO THE POOL HEATER |
| | SHALL BE 1 1/2" PER 2014 FBC-RES.TABLE G2413.4 (1) AND |
| | THE CSST SHALL BE 2" PER TABLE G2413.4 (5). |
| | 8) SUBMIT TWO COPIES OF OF MANUFACTURER'S |
| | SPECIFICATIONS FOR ALL GAS APPLIANCES. THE ONLY SPECS |
| | SUBMITTED WERE FOR THE FIREPLACE. APPLIANCES SHALL BE |
| | LISTED AND LABELED PER 2014 FBC-RES. SEC. G2404.3. |
| | 9) SHOW THE CORRELATING EHD OF THE CSST TO ENSURE |
| | CORRECT SIZING. |
| | |
| | I SUGGEST YOU CALL TO MAKE AN APPOINTMENT TO GO OVER |
| | THE GAS DRAWING. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |