| Notes |
| Date |
Text |
| 2015-08-20 04:19:12 | 1) SUBMIT A GAS RISER DIAGRAM FOR REVIEW. WPB AMEND. TO | | | FBC SEC. 107.2.1., 107.3.5.3. | | | 2) SUBMIT TWO COPIES OF MANUF. SPECIFICATIONS FOR ALL | | | GAS APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED. | | | FBC-R SEC. G2404.3. | | | 3) INDICATE PSI OF THE SYSTEM, TYPE OF PIPE TO BE USED, | | | DISTANCE FROM METER TO MOST REMOTE OUTLET, SIZING TABLE | | | USED TO SUPPLY GAS. REFER TO FBC-FUEL GAS SEC.G2413.3. | | | 4) SUBMIT CALCULATIONS FOR CCOMBUSTION AIR FOR THE | | | INTERIOR APPLIANCES. FBC-FUEL GAS SEC. G2407. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|