2015-09-25 17:29:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FIRST FLOOR DEN/BEDROOM AND FIRST FLOOR LEVEL
 REQUIRE SMOKE ALARMS. FBC-R314.3 SMOKE ALARMS SHALL BE
 INSTALLED IN THE FOLLOWING LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
 WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM
 DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT
 THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE
 ALARMS IN THE INDIVIDUAL UNIT.
  
 2) FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN
 10 FEET OF EACH SLEEPING ROOM.
  
 3) E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO
 THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR
 LINE OF ANY WALL SPACE IS MORE THAN 6 FEET (1829 MM),
 FROM A RECEPTACLE OUTLET. IT APPEARS THAT THE REQUIRED
 SPACING HAS BEEN EXCEEDED ON THE FIRST FLOOR. E3901.2.3
 FLOOR RECEPTACLES.
 RECEPTACLE OUTLETS IN FLOORS SHALL NOT BE COUNTED AS
 PART OF THE REQUIRED NUMBER OF RECEPTACLE OUTLETS
 EXCEPT WHERE LOCATED WITHIN 18 INCHES (457 MM) OF THE
 WALL.
  
 4) E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE
 RECEPTACLES INSTALLED IN GARAGES AND GRADE-LEVEL
 PORTIONS OF UNFINISHED ACCESSORY BUILDINGS USED FOR
 STORAGE OR WORK AREAS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. GARAGE
 DOOR RECEPTACLES ARE REQUIRED TO BE GFCI PROTECTED.
  
 5) E3609.3 BONDING FOR OTHER SYSTEMS.
 AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING CONDUCTORS REQUIRED FOR OTHER
 SYSTEMS SHALL BE PROVIDED EXTERNAL TO ENCLOSURES AT THE
 SERVICE EQUIPMENT OR METERING EQUIPMENT ENCLOSURE AND
 AT THE DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS
 OR STRUCTURES.
  
 6) E3609.7 BONDING OTHER METAL PIPING.
 WHERE INSTALLED IN OR ATTACHED TO A BUILDING OR
 STRUCTURE, METAL PIPING SYSTEMS, INCLUDING GAS PIPING,
 CAPABLE OF BECOMING ENERGIZED SHALL BE BONDED TO THE
 SERVICE EQUIPMENT ENCLOSURE, THE GROUNDED CONDUCTOR AT
 THE SERVICE, THE GROUNDING ELECTRODE CONDUCTOR WHERE OF
 SUFFICIENT SIZE, OR TO THE ONE OR MORE GROUNDING
 ELECTRODES USED.
  
 7) E3901.12 HVAC OUTLET. A 125-VOLT, SINGLE-PHASE, 15-
 OR 20- AMPERE-RATED RECEPTACLE OUTLET SHALL BE
 INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING
 OF HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME
 LEVEL AND WITHIN 25 FEET (7620 MM) OF THE HEATING,
 AIR-CONDITIONING AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE OUTLET SHALL NOT BE CONNECTED TO THE LOAD
 SIDE OF THE HVAC EQUIPMENT DISCONNECTING MEANS.
  
 8) ELECTRICAL GENERAL NOTE 12 ON E101 REFERENCES THE
 2008 NEC AND SHOULD REFERENCE FBCR E3902.12.
  
 9) ELECTRICAL OUTLET NOTE 3 ON E101 REFERENCES THE 2011
 NEC 210.52 (WRONG SECTION FOR TAMPER RESISTANT
 RECEPTACLES) AND SHOULD REFERENCE FBCR E4002.14.
  
  
  
  