| 2015-09-25 17:29:06 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY ELECTRICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE FIRST FLOOR DEN/BEDROOM AND FIRST FLOOR LEVEL |
| | REQUIRE SMOKE ALARMS. FBC-R314.3 SMOKE ALARMS SHALL BE |
| | INSTALLED IN THE FOLLOWING LOCATIONS: |
| | 1. IN EACH SLEEPING ROOM. |
| | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| | WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| | INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM |
| | DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| | THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| | ALARMS IN THE INDIVIDUAL UNIT. |
| | |
| | 2) FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN |
| | 10 FEET OF EACH SLEEPING ROOM. |
| | |
| | 3) E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO |
| | THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR |
| | LINE OF ANY WALL SPACE IS MORE THAN 6 FEET (1829 MM), |
| | FROM A RECEPTACLE OUTLET. IT APPEARS THAT THE REQUIRED |
| | SPACING HAS BEEN EXCEEDED ON THE FIRST FLOOR. E3901.2.3 |
| | FLOOR RECEPTACLES. |
| | RECEPTACLE OUTLETS IN FLOORS SHALL NOT BE COUNTED AS |
| | PART OF THE REQUIRED NUMBER OF RECEPTACLE OUTLETS |
| | EXCEPT WHERE LOCATED WITHIN 18 INCHES (457 MM) OF THE |
| | WALL. |
| | |
| | 4) E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES. |
| | ALL 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE |
| | RECEPTACLES INSTALLED IN GARAGES AND GRADE-LEVEL |
| | PORTIONS OF UNFINISHED ACCESSORY BUILDINGS USED FOR |
| | STORAGE OR WORK AREAS SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. GARAGE |
| | DOOR RECEPTACLES ARE REQUIRED TO BE GFCI PROTECTED. |
| | |
| | 5) E3609.3 BONDING FOR OTHER SYSTEMS. |
| | AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| | INTERSYSTEM BONDING CONDUCTORS REQUIRED FOR OTHER |
| | SYSTEMS SHALL BE PROVIDED EXTERNAL TO ENCLOSURES AT THE |
| | SERVICE EQUIPMENT OR METERING EQUIPMENT ENCLOSURE AND |
| | AT THE DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS |
| | OR STRUCTURES. |
| | |
| | 6) E3609.7 BONDING OTHER METAL PIPING. |
| | WHERE INSTALLED IN OR ATTACHED TO A BUILDING OR |
| | STRUCTURE, METAL PIPING SYSTEMS, INCLUDING GAS PIPING, |
| | CAPABLE OF BECOMING ENERGIZED SHALL BE BONDED TO THE |
| | SERVICE EQUIPMENT ENCLOSURE, THE GROUNDED CONDUCTOR AT |
| | THE SERVICE, THE GROUNDING ELECTRODE CONDUCTOR WHERE OF |
| | SUFFICIENT SIZE, OR TO THE ONE OR MORE GROUNDING |
| | ELECTRODES USED. |
| | |
| | 7) E3901.12 HVAC OUTLET. A 125-VOLT, SINGLE-PHASE, 15- |
| | OR 20- AMPERE-RATED RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING |
| | OF HEATING, AIR-CONDITIONING AND REFRIGERATION |
| | EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME |
| | LEVEL AND WITHIN 25 FEET (7620 MM) OF THE HEATING, |
| | AIR-CONDITIONING AND REFRIGERATION EQUIPMENT. THE |
| | RECEPTACLE OUTLET SHALL NOT BE CONNECTED TO THE LOAD |
| | SIDE OF THE HVAC EQUIPMENT DISCONNECTING MEANS. |
| | |
| | 8) ELECTRICAL GENERAL NOTE 12 ON E101 REFERENCES THE |
| | 2008 NEC AND SHOULD REFERENCE FBCR E3902.12. |
| | |
| | 9) ELECTRICAL OUTLET NOTE 3 ON E101 REFERENCES THE 2011 |
| | NEC 210.52 (WRONG SECTION FOR TAMPER RESISTANT |
| | RECEPTACLES) AND SHOULD REFERENCE FBCR E4002.14. |
| | |
| | |
| | |
| | |