Plan Review Notes
Plan Review Notes For Permit 15080251
Permit Number 15080251
Review Stop E
Sequence Number 1
Notes
Date Text
2015-08-13 15:03:06PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. DEFINE YOUR SCOPE OF WORK ON THE DRAWINGS FOR
 APPROVAL. THE APPLICABLE NEC IN EFFECT IS THE 2011
 EDITION.
 2. FROM LOOKING AT THE ELECTRICAL RISER AS SHOWN IT
 APPEARS THAT YOU HAVE TAPPED INTO THE 2/0 CU CONDUCTORS
 TO FEED THE 60 AMP SUB PANEL. YOU SHALL SUBMIT A
 CORRECTED AND SITE SPECIFIC RISER DIAGRAM.
 3. YOU SHALL SUBMIT AN ACCURATE CIRCUIT DIRECTORY AS
 DESCRIBED IN NEC 408.4 FOR BOTH THE MAIN AND THE SUB
 PANEL.
 4. YOU SHALL SUBMIT LOAD CALCS FOR THE SUB PANEL.
 5. FROM THE SUBMITTED DRAWING, IT APPEARS THAT THE
 TANKLESS WATER HEATER IS CLOSER TO THE GAS METER THAN
 THE MINIMUM 3' REQUIRED BY NFPA 54 SECTION 5.8.6.1
 6. DUE TO THE ATTACHED GARAGE AND THE GAS APPLIANCES,
 YOU SHALL COME INTO COMPLIANCE WITH FBC-R 315 CARBON
 MONOXIDE DETECTORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  