| 2015-10-20 14:32:21 | ****CORRECTIONS**** |
| | REVISED 11/9/15 (SEE NEW COMMENT) |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. OPENING DIMENSIONS AND NOTES UNDER "GENERAL SCOPE OF |
| | WORK" ARE TOO SMALL TO BE LEGIBLE. INCREASE FONT SIZE |
| | FOR THESE ITEMS, FBC 107. |
| | |
| | 2. REVISE THE INSTALLATION SCHEDULE AS FOLLOWS: |
| | |
| | A. SHUTTER MOUNTING CONNECTION TYPE SHOULD CORRELATE |
| | WITH THE ANCHOR CHARTS IN THE PRODUCT APPROVAL; FOR |
| | EXAMPLE, SEE SHEET 11. SECTIONS (CONNECTION TYPES) ARE |
| | NAMED 1(TOP), 1(BOTTOM), 2(TOP), 2(BOTTOM), ETC. |
| | |
| | B. IF INSTALLATION IS VERTICAL, SPANS SHOULD BE THE |
| | DIMENSION ANCHOR TO ANCHOR, SO SHOULD BE OPENING HEIGHT |
| | PLUS EDGE DISTANCE TOP AND BOTTOM. SPANS APPEAR TO |
| | CORRELATE WITH THE HORIZONTAL DIMENSION, THE WIDTH. |
| | |
| | WITHOUT THE CONNECTION TYPE AND SPAN, IT IS NOT |
| | POSSIBLE TO DETERMINE CODE COMPLIANCE. |
| | |
| | 3. WHEN RESUBMITTING, REVISE THE APPLICATION TO BE |
| | CONSISTENT WITH THE SCOPE OF WORK STATED (STILL STATES |
| | WINDOW AND DOOR REPLACEMENT). |
| | |
| | 4. WHEN RESUBMITTING, COLLATE TWO IDENTICAL SETS OF |
| | PERMIT DOCUMENTS FOR PERMIT ISSUANCE. |
| | |
| | ***NEW COMMENT*** |
| | |
| | 5. RESUBMITTAL FORM STATES THAT "EXISTING WINDOWS TO |
| | REMAIN." WINDOWS WERE REPLACED WITHOUT A PERMIT AND |
| | THEREFORE A CODE CASE WAS GENERATED. THE WINDOWS |
| | INSTALLED WITHOUT PERMIT REQUIRE A PERMIT. THEY ARE NOT |
| | CONSIDERED "EXISTING" AS THEY HAVE NOT BEEN PERMITTED |
| | AND INSPECTED AND THEY DO NOT COMPLY WITH FBC |
| | REQUIREMENTS (LACKING IMPACT PROTECTION). |
| | |
| | |
| | |
| | |
| | |
| | |