| 2015-08-11 07:46:36 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | SUBMIT A FLOORING UNDERLAYMENT SPEC SHEET AND TEST | | | RESULTS THAT MEETS THE REQUIREMENTS OF: | | | | | | FBC 603.1 FLAME SPREAD IN A TYPE I OR II BUILDING, | | | | | | AND | | | | | | FBC 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|