| 2015-08-27 07:11:53 | 1) THE PLANS REFER TO THE 2010 FBC. THE CODE IN EFFECT |
| | FOR THIS PERMIT IS THE 2014 FBC-RESIDENTIAL. REVISE THE |
| | PLANS TO REFLECT COMPLIANCE WITH THE 2014 CODE. NOTE - |
| | THE CHAPTER NUMBER HAS CHANGED IN THE CODE . PLEASE |
| | REFERENCE THE CORRECT CHAPTER AND CODE SECTION ON THE |
| | PLANS. |
| | 2) SUBMIT A PUMP CURVE FOR THE PENTAIR PUMP TO VERIFY |
| | COMPLIANCE WITH ANSI/APSP-7 AND 2014 FBC SEC.R4501.6.3. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL |
| | MAIN DRAIN AND OUTLET COVER. MAIN DRAIN SUCTION OUTLET |
| | AND COVER/GRATE SHALL BE TESTED AND LISTED BY A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY AND COMPLY |
| | WITH ASME/ANSI A112.19.8. |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL |
| | HEATER.2014 FBC-ENERGY - SEC. R403.9.1.1 - ALL GAS AND |
| | SPA HEATERS SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF |
| | 82 % FOR HEATERS MANUFACTURED ON OR AFTER APRIL 16, |
| | 2013 WHEN TESTED IN ACCORDANCE WITH ANSI Z 21.56. POOL |
| | HEATERS FIRED BY NATURAL OR LP GAS SHALL NOT HAVE |
| | CONTINUOUSLY BURNING PILOT LIGHTS. |
| | 5) 2014 FBC- ENERGY- SEC. R 403.9.3. - HEATED SWIMMING |
| | POOLS AND IN GROUND PERMANENTLY INSTALLED SPAS SHALL BE |
| | EQUIPPED WITH A VAPOR-RETARDANT COVER ON OR AT THE |
| | WATER SURFACE OR A LIQUID COVER OR OTHER MEANS PROVEN |
| | TO REDUCE HEAT LOSS. |
| | 6) SHT. 2 - THE PIPING SCHEMATIC AND THE PLAN VIEW SHOW |
| | A 2 1/2" RETURN LINE BUT ON THE "ASSUMPTIONS" REFERENCE |
| | IS MADE TO A 2" RETURN LINE. CLARIFY. |
| | SHT. 2 - SIZE THE RETURN LINE IN ITS ENTIRETY ON THE |
| | PLAN VIEW.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 7) SUBMIT A PIPING SCHEMATIC FOR THE BADU-JET |
| | SYSTEM..WPB AMEND. TO FBC SEC. 107.2.1. |
| | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE BADU - |
| | JET MAIN DRAIN & PUMP & SUBMIT PUMP CURVE. |
| | 9) THE PIPING SCHEMATIC ON SHT. 2 SHOWS 2 SUCTION |
| | OUTLETS YET THIS IS OMITTED ON THE MAIN DRAIN DETAIL. |
| | CLARIFY. |
| | |