Plan Review Notes
Plan Review Notes For Permit 15080178
Permit Number 15080178
Review Stop B
Sequence Number 3
Notes
Date Text
2015-11-10 15:05:18BUILDING PLAN REVIEW
 W. P. B. PERMIT:15080178 / NEW 7/11 BUILDING
 ADD: 2100 45TH ST.
 CONT: TBD/ TO BE DETERMINED
 TEL: (???)???-????
 E-MAIL:????????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 3RD REVIEW
 DATE: FRI. OCT. 16/ 2015
 ACTION: DENIED
  
 ) NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 1) COMPLIED. (3) SOILS REPORTS.
  
 2) 3RD REQUEST. RESIDENT INSPECTOR PROGRAM. SHEET S0.0
 ALSO INDICATES REQUIRED SPECIAL INSPECTIONS. PLEASE
 NOTE A RESIDENT INSPECTOR SHALL BE REQUIRED FOR THIS
 JOB. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
 STRUCTURAL MASONRY
 STRUCTURAL CONCRETE
 FIELD WELDING
 STRUCTURAL STEEL/ BOLTED CONNECTIONS
  
 2A) 3RD REQUEST. RESPONSE INDICATES FORMS HAVE BEEN
 RECEIVED. WE NEED A E-MAIL ADDRESS TO BE ABLE TO SEND
 THE RESIDENT INSPECTOR FORMS TO BE FILED OUT. RESIDENT
 INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES NOTARIZED
 AND RETURNED TO THE BUILDING DEPARTMENT.
 RESIDENT INSPECTOR FORMS E-MAILED TO:
 [email protected] 10/16/2015 09:59 AM
  
 2B) 3RD REQUEST. FOR THE RESIDENT INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
 CONTACT: KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2C) 3RD REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS
 MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 2D) 3RD REQUEST. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE RESIDENT INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
  
 2E) 3RD REQUEST. NOTICE ONLY! PLEASE CALL THE CITY OF
 WEST PALM BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE
 (561) 805-6700) FOR IN-PROGRESS INSPECTIONS FOR
 AUDITING OF JOBSITE INSPECTIONS.
  
 3) 3RD REQUEST. SHEET S0.0 THE PRESSURES FOR ZONES 1-5
 ARE INDICATED IN VASD, ALLOWABLE DESIGN PRESSURES. THE
 ROOF PRESSURES ARE RIGHT ON, THE WALL PRESSURES SHOWN
 ARE A LITTLE LOW FOR THE TRIBUTARY AREAS SHOWN.
 1609.4.4.1. COMPONENTS & CLADDING.
  
 4) SHEET S4.0 THE WALL PRESSURES FOR ZONES 4 AND 5
 APPEAR TO BE LOW FOR A MEAN ROOF HEIGHT OF 15 FT,
 EXPOSURE C FOR WALL ZONES 4 & 5. NEGATIVE PRESSURES ARE
 TAKEN AT THE ROOF HEIGHT OF 15 FT.
 2014 FBC-B TABLE 1609.6.2
 2014 FBC-B TABLE 1609.7.2
  
 5) COMPLIED. UNDER SEPARATE PERMIT AND REVIEW. SHEET
 S4.0 ALSO INDICATES THE USE OF A HORIZONTAL AWNING
 CANOPY, THERE IS NO DESIGN CRITERIA FOR THE CANOPY.
 2014 FBC-B 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS.
  
 6) COMPLIED. UNDER A SEPARATE PERMIT AND REVIEW. SHEET
 S5.1 THE MONUMENT SIGN DETAILS. NOTE SIGNS REQUIRE A
 SEPARATE PERMIT AND WILL BE REVIEWED UNDER THE SIGN
 PERMIT. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) 3RD REQUEST. PLEASE NOTE THE PRODUCT APPROVALS HAVE
 NOT BEEN REVIEWED BY THE DESIGNER OF RECORD, NO SHOP
 DRAWING STAMP OF APPROVAL HAS BEEN AFFIXED. THE PERMIT
 EXPEDITER HAS JUST LIMPED THESE APPROVALS TOGETHER,
 THEY ARE NOT STAPLED, THEY ARE NOT MARKED WHICH ARE OLD
 AND WHICH ARE NEW.
 THERE WILL BE ISSUES WITH THE APPROVALS THAT WILL TAKE
 TO LONG OF A TIME PERIOD TRYING TO GUESS WHAT IS
 WHAT!!!!!
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS
 E) STORM SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
  
 3RD REVIEW PRODUCTS NOT REVIEWED NOT STAPLED, COLLATED:
 EXTERIOR DOORS, THERE WERE 2 REPORTS SUBMITTED NOA
 14-0602 ALUMINUM STOREFRONT DOOR LARGE MISSILE IMPACT
 AND NOA 14-0811.22
 NON-IMPACT OS DOOR AND STORE FRONT PLEASE SHOW WHERE
 THE LARGE MISSILE IMPACT DOOR WILL BE INSTALLED. STORM
 SHUTTERS WILL BE REQUIRED FOR THE NON-IMPACT GLAZING IN
 THE STOREFRONT WALL AND DOOR SYSTEM!!!!!
  
 A PRODUCT APPROVAL FOR STORM SHUTTERS WILL ALSO BE
 REQUIRED. PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.2.
  
 FL BLD CODE 2010 SECTION 107.2.5., 1609.1.2, 1715.8 A
 COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC.,
 SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO
 FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
 FOR ALL GLAZING UNITS IDENTIFY THE TYPE OF GLAZING,
 MULLION TYPES, WIDTH, HEIGHT OF UNITS TYPES OF
 FASTENERS, PRESSURES FOR UNITS.
  
 ROOFING PRODUCT APPROVAL SUBMITTED NOA 13-0419.05 PAGE
 08 MAXIMUM DESIGN PRESSURE OF -45 AND LIMITATION NUMBER
 9 NO ENHANCED FASTENING IS ALLOWED!!!!!!!
  
 SKYLIGHT REPORT PTC IS A OLD 2007 REPORT UNDER RULE 9B.
 PLEASE NOTE RULE 9B ENDED OCT 31/ 2010. RULE 9N-3
 REPLACED THIS RULE NOV.01/2010. THERE HAS BEEN 2 CODE
 CYCLES THE 2010 AND 2014 FBC, PLEASE UPDATE EVALUATION
 REPORT. NOTE THE NOA 08-0305.02 POLYCARBONATE IS A
 EXPIRED REPORT ALSO.
  
 NOTICE!!!!!. CARRIER ROOF TOP CURBS NOA 15-0218.11
 PLEASE BE AWARE THERE IS A ISSUE WITH THE RESTRAINT
 BRACKET SHOWN ON SHEET 2 OF 5, ALSO SEE DETAIL OF
 RESTRAINT BRACKET ON SHEET 5 OF 5. SHEET 2 OF 5
 INDICATES (7) # 10 TEK SCREWS THAT ARE TO HOLD THE
 RESTRAINT BRACKET TO THE ROOF CURB. PAGE 5 SHOWS THE
 BRACKET DOES NOT TURN DOWN THE INTERIOR OF THE CURB.
 HOW WILL THE RESTRAINT BRACKET BE HELD TO THE CURB.
 NOA 14-0513.10 IS FOR THE ROOFTOP FANS, NO PRODUCT
 APPROVALS WAS SUBMITTED FOR THE CURB. HIGHLIGHT CIRCLE
 TYPE OF UNIT AND PRESSURES. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 THE CITY HAS RECEIVED THE LETTER FROM THYBAR ABOUT THE
 CHANGE IN CONFIGURATION THE BRACKET FROM THE CURB TO
 THE RTU ROOF TOP UNIT. CONTACTING MIAMI-DADE?S OFFICE
 THEY INDICATED ON SHEET 5 OF 5 NOTE: RESTRAINT BRACKET
 IS TO BE DETERMINED BY PROJECT SPECIFIC CALCULATIONS BY
 A FLORIDA LICENSED PE OF FLORIDA REGISTERED ARCHITECT.
  
 8) 3RD REVIEW. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 9) COMPLIED. SHEETS A4.0 & A4.1 BOTH SHOW THE USE OF
 VENEER STONE (V1) ON THE EXTERIOR OF THE BUILDING.
 SHEET A6.0 DETAIL # 3 SHOWS HOW THE PLACEMENT OF VENEER
 STONE, MONOLITHIC FOUNDATION SLAB AND THE CONCRETE
 SIDEWALK AND THE EXPANSION JOINT HIDDEN BENEATH THE
 BUILT OUT WALL WHERE THE VENEER STONE IS INSTALLED.
 2014 FBC-B 1403.8 & 2114.2.
  
 10) COMPLIED. SHEET A4.1 INDICATES THE USE OF ROOF TOP
 LADDERS, PLEASE PROVIDE COMPLIANCE WITH SECTION
 1509.6.4 2014 FBC-B
  
 ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877
 MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT
 APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE
 FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE.
  
 11) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 PLEASE NOTE THAT A BUILDING WILL BE DEMOLISHED AT THIS
 SITE, PLEASE MAKE SURE THEY GIVE YOU THE SQUARE FOOT
 CREDIT.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  