| 2015-11-10 15:05:18 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:15080178 / NEW 7/11 BUILDING |
| | ADD: 2100 45TH ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: (???)???-???? |
| | E-MAIL:???????????????? |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 3RD REVIEW |
| | DATE: FRI. OCT. 16/ 2015 |
| | ACTION: DENIED |
| | |
| | ) NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | 1) COMPLIED. (3) SOILS REPORTS. |
| | |
| | 2) 3RD REQUEST. RESIDENT INSPECTOR PROGRAM. SHEET S0.0 |
| | ALSO INDICATES REQUIRED SPECIAL INSPECTIONS. PLEASE |
| | NOTE A RESIDENT INSPECTOR SHALL BE REQUIRED FOR THIS |
| | JOB. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| | |
| | FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | STRUCTURAL MASONRY |
| | STRUCTURAL CONCRETE |
| | FIELD WELDING |
| | STRUCTURAL STEEL/ BOLTED CONNECTIONS |
| | |
| | 2A) 3RD REQUEST. RESPONSE INDICATES FORMS HAVE BEEN |
| | RECEIVED. WE NEED A E-MAIL ADDRESS TO BE ABLE TO SEND |
| | THE RESIDENT INSPECTOR FORMS TO BE FILED OUT. RESIDENT |
| | INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES NOTARIZED |
| | AND RETURNED TO THE BUILDING DEPARTMENT. |
| | RESIDENT INSPECTOR FORMS E-MAILED TO: |
| | [email protected] 10/16/2015 09:59 AM |
| | |
| | 2B) 3RD REQUEST. FOR THE RESIDENT INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| | CONTACT: KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 2C) 3RD REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS |
| | MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 2D) 3RD REQUEST. NOTE FOR PAPER PLANS 3 SETS OF |
| | DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT |
| | ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE RESIDENT INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS. |
| | |
| | 2E) 3RD REQUEST. NOTICE ONLY! PLEASE CALL THE CITY OF |
| | WEST PALM BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE |
| | (561) 805-6700) FOR IN-PROGRESS INSPECTIONS FOR |
| | AUDITING OF JOBSITE INSPECTIONS. |
| | |
| | 3) 3RD REQUEST. SHEET S0.0 THE PRESSURES FOR ZONES 1-5 |
| | ARE INDICATED IN VASD, ALLOWABLE DESIGN PRESSURES. THE |
| | ROOF PRESSURES ARE RIGHT ON, THE WALL PRESSURES SHOWN |
| | ARE A LITTLE LOW FOR THE TRIBUTARY AREAS SHOWN. |
| | 1609.4.4.1. COMPONENTS & CLADDING. |
| | |
| | 4) SHEET S4.0 THE WALL PRESSURES FOR ZONES 4 AND 5 |
| | APPEAR TO BE LOW FOR A MEAN ROOF HEIGHT OF 15 FT, |
| | EXPOSURE C FOR WALL ZONES 4 & 5. NEGATIVE PRESSURES ARE |
| | TAKEN AT THE ROOF HEIGHT OF 15 FT. |
| | 2014 FBC-B TABLE 1609.6.2 |
| | 2014 FBC-B TABLE 1609.7.2 |
| | |
| | 5) COMPLIED. UNDER SEPARATE PERMIT AND REVIEW. SHEET |
| | S4.0 ALSO INDICATES THE USE OF A HORIZONTAL AWNING |
| | CANOPY, THERE IS NO DESIGN CRITERIA FOR THE CANOPY. |
| | 2014 FBC-B 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS. |
| | |
| | 6) COMPLIED. UNDER A SEPARATE PERMIT AND REVIEW. SHEET |
| | S5.1 THE MONUMENT SIGN DETAILS. NOTE SIGNS REQUIRE A |
| | SEPARATE PERMIT AND WILL BE REVIEWED UNDER THE SIGN |
| | PERMIT. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 7) 3RD REQUEST. PLEASE NOTE THE PRODUCT APPROVALS HAVE |
| | NOT BEEN REVIEWED BY THE DESIGNER OF RECORD, NO SHOP |
| | DRAWING STAMP OF APPROVAL HAS BEEN AFFIXED. THE PERMIT |
| | EXPEDITER HAS JUST LIMPED THESE APPROVALS TOGETHER, |
| | THEY ARE NOT STAPLED, THEY ARE NOT MARKED WHICH ARE OLD |
| | AND WHICH ARE NEW. |
| | THERE WILL BE ISSUES WITH THE APPROVALS THAT WILL TAKE |
| | TO LONG OF A TIME PERIOD TRYING TO GUESS WHAT IS |
| | WHAT!!!!! |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. |
| | |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS |
| | E) STORM SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | |
| | 3RD REVIEW PRODUCTS NOT REVIEWED NOT STAPLED, COLLATED: |
| | EXTERIOR DOORS, THERE WERE 2 REPORTS SUBMITTED NOA |
| | 14-0602 ALUMINUM STOREFRONT DOOR LARGE MISSILE IMPACT |
| | AND NOA 14-0811.22 |
| | NON-IMPACT OS DOOR AND STORE FRONT PLEASE SHOW WHERE |
| | THE LARGE MISSILE IMPACT DOOR WILL BE INSTALLED. STORM |
| | SHUTTERS WILL BE REQUIRED FOR THE NON-IMPACT GLAZING IN |
| | THE STOREFRONT WALL AND DOOR SYSTEM!!!!! |
| | |
| | A PRODUCT APPROVAL FOR STORM SHUTTERS WILL ALSO BE |
| | REQUIRED. PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC |
| | ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT |
| | GLAZING. FBC 1609.1.2. |
| | |
| | FL BLD CODE 2010 SECTION 107.2.5., 1609.1.2, 1715.8 A |
| | COMPLETE INSTALLATION SCHEDULE SUMMARIZING & |
| | IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING |
| | REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC., |
| | SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO |
| | FACILITATE PLAN REVIEW AND PERMIT ISSUANCE. |
| | |
| | FOR ALL GLAZING UNITS IDENTIFY THE TYPE OF GLAZING, |
| | MULLION TYPES, WIDTH, HEIGHT OF UNITS TYPES OF |
| | FASTENERS, PRESSURES FOR UNITS. |
| | |
| | ROOFING PRODUCT APPROVAL SUBMITTED NOA 13-0419.05 PAGE |
| | 08 MAXIMUM DESIGN PRESSURE OF -45 AND LIMITATION NUMBER |
| | 9 NO ENHANCED FASTENING IS ALLOWED!!!!!!! |
| | |
| | SKYLIGHT REPORT PTC IS A OLD 2007 REPORT UNDER RULE 9B. |
| | PLEASE NOTE RULE 9B ENDED OCT 31/ 2010. RULE 9N-3 |
| | REPLACED THIS RULE NOV.01/2010. THERE HAS BEEN 2 CODE |
| | CYCLES THE 2010 AND 2014 FBC, PLEASE UPDATE EVALUATION |
| | REPORT. NOTE THE NOA 08-0305.02 POLYCARBONATE IS A |
| | EXPIRED REPORT ALSO. |
| | |
| | NOTICE!!!!!. CARRIER ROOF TOP CURBS NOA 15-0218.11 |
| | PLEASE BE AWARE THERE IS A ISSUE WITH THE RESTRAINT |
| | BRACKET SHOWN ON SHEET 2 OF 5, ALSO SEE DETAIL OF |
| | RESTRAINT BRACKET ON SHEET 5 OF 5. SHEET 2 OF 5 |
| | INDICATES (7) # 10 TEK SCREWS THAT ARE TO HOLD THE |
| | RESTRAINT BRACKET TO THE ROOF CURB. PAGE 5 SHOWS THE |
| | BRACKET DOES NOT TURN DOWN THE INTERIOR OF THE CURB. |
| | HOW WILL THE RESTRAINT BRACKET BE HELD TO THE CURB. |
| | NOA 14-0513.10 IS FOR THE ROOFTOP FANS, NO PRODUCT |
| | APPROVALS WAS SUBMITTED FOR THE CURB. HIGHLIGHT CIRCLE |
| | TYPE OF UNIT AND PRESSURES. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | THE CITY HAS RECEIVED THE LETTER FROM THYBAR ABOUT THE |
| | CHANGE IN CONFIGURATION THE BRACKET FROM THE CURB TO |
| | THE RTU ROOF TOP UNIT. CONTACTING MIAMI-DADE?S OFFICE |
| | THEY INDICATED ON SHEET 5 OF 5 NOTE: RESTRAINT BRACKET |
| | IS TO BE DETERMINED BY PROJECT SPECIFIC CALCULATIONS BY |
| | A FLORIDA LICENSED PE OF FLORIDA REGISTERED ARCHITECT. |
| | |
| | 8) 3RD REVIEW. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 9) COMPLIED. SHEETS A4.0 & A4.1 BOTH SHOW THE USE OF |
| | VENEER STONE (V1) ON THE EXTERIOR OF THE BUILDING. |
| | SHEET A6.0 DETAIL # 3 SHOWS HOW THE PLACEMENT OF VENEER |
| | STONE, MONOLITHIC FOUNDATION SLAB AND THE CONCRETE |
| | SIDEWALK AND THE EXPANSION JOINT HIDDEN BENEATH THE |
| | BUILT OUT WALL WHERE THE VENEER STONE IS INSTALLED. |
| | 2014 FBC-B 1403.8 & 2114.2. |
| | |
| | 10) COMPLIED. SHEET A4.1 INDICATES THE USE OF ROOF TOP |
| | LADDERS, PLEASE PROVIDE COMPLIANCE WITH SECTION |
| | 1509.6.4 2014 FBC-B |
| | |
| | ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND |
| | APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR |
| | ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877 |
| | MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT |
| | APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE |
| | FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND |
| | APPLIANCES? LEVEL SERVICE SPACE. |
| | |
| | 11) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | PLEASE NOTE THAT A BUILDING WILL BE DEMOLISHED AT THIS |
| | SITE, PLEASE MAKE SURE THEY GIVE YOU THE SQUARE FOOT |
| | CREDIT. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |