| Plan Review Notes For Permit 15080178 |
| Permit Number |
15080178 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-04 08:53:39 | 1) THE SUBMITTED ENGINEERING FOR THE CO2 TANK ARE | | | COPIES AND CANNOT BE ACCEPTED.FL. ADMIN. CODE RULE | | | 62G15-23.002 REQUIRES A SEAL AND WET SIGNATURE. | | | 2) THE CIRCLED WIND LOAD IS FOR 140 MPH AND THE WIND | | | ZONE FOR THIS AREA IS 170 MPH. | | | 3)THE CALCULATIONS FOR THE SCHIER GREASE TRAP SHALL BE | | | REVIEWED BY SCHIER TO ENSURE CORRECT SIZING.2014 | | | FBC-PLUMBING SEC.1003.2. PLEASE CONTACT LEE | | | SCHNEEWEISS, SCHIER REPRESENTATIVE AT | | | 1-800-538-4792.2ND REQUEST. | | | 4) SUBMIT ELEVATION DETAILS FOR THE DRINKING | | | FOUNTAIN.COMPLY WITH 2014 FBC-ACCESSIBILITY SECS.306 & | | | 602. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|