| 2015-10-08 07:35:31 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15080178 | | | 10/8/15 | | | | | | 1) THE PREVIOUSLY SUBMITTED ENERGY CALCULATIONS WERE | | | NOT RE-SUBMITTED WITH THE CORRECTED PLANS- REFER TO | | | SECTIONS C101.3 & C101.5 FBC-14 ENERGY CONSERVATION AND | | | PROVIDE THE CALCULATIONS. | | | 2) SHEET M1.1, DETAIL #5: SPECIFY THE THE TYPE, SIZE, | | | AND SPACING OF THE CURB ANCHOR BOLTS. | | | 3) THE SUBMITTED NOA'S FOR THE ROOF TOP EQUIPMENT ARE | | | INCOMPLETE. A) AC STAND NOA #13-1017.09: PAGES | | | 3,4,6,7,8, & 9 OF INSTALLATION DETAILS ARE MISSING. THE | | | REMAINING INSTALLATION PAGES WERE REDUCED IN SIZE AND | | | HAVE PRINT THAT IS TOO SMALL TO READ AND TO SCAN INTO | | | THE BUILDING DEPARTMENT COMPUTER FILES. B) GREENHECK | | | FAN #14-0513.10: INSTALLATION PAGES 1-7 HAVE PRINT TOO | | | SMALL TO READ OR TO SCAN. C) THYBAR CORP. CURB | | | #15-0218.11: INSTALL. SHEETS 1-5 HAVE PRINT TOO SMALL | | | TO READ OR SCAN. PLEASE REFER TO SECTION 107.2.1 WPB | | | AMENDMENTS TO THE FLORIDA BUILDING CODE AND PROVIDE | | | LEGIBLE DOCUMENTS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|