Plan Review Notes
Plan Review Notes For Permit 15080178
Permit Number 15080178
Review Stop P
Sequence Number 1
Notes
Date Text
2015-08-28 11:00:131) A MINIMUM OF 2 DRINKING FOUNTAINS ARE REQUIRED IN
 ACCORDANCE WITH TABLE 403.1 AND FOOTNOTE (E) OF THE
 2014 FBC-PLUMBING AND ALSO FBC-ACCESSIBILITY SEC.
 211.2.
 2) SHT. A2.0 - SUBMIT ENGINEERING ON THE ANCHORING OF
 THE CO2 TANK. THE ANCHORING SHALL BE DESIGNED FOR 170
 MPH V ULT EXPOSURE B.
 3) THE BEVERAGE AND COFFEE MACHINES AND NONCARBONATED
 BEVERAGE DISPENSERS SHALL BE EQUIPPED WITH BACKFLOW
 PREVENTERS COMPLYING WITH ASSE 1022 PER THE 2014
 FBC-PLUMBING SECS.608.16.1 & 608.16.10.
 3) THE CALCULATIONS FOR THE SCHIER GREASE TRAP SHALL BE
 REVIEWED BY SCHIER TO ENSURE CORRECT SIZING.2014
 FBC-PLUMBING SEC.1003.2. PLEASE CONTACT LEE
 SCHNEEWEISS, SCHIER REPRESENTATIVE AT 1-800-538-4792.
 4) SHT. A2.2 - SUBMIT ROOF DRAINAGE CALCULATIONS. THE
 CALCULATIONS SHALL INCLUDE 1/2 THE AREA OF ANY VERTICAL
 WALL (PARAPET) THAT DIVERTS RAINWATTER TO THE ROOF. THE
 SCUPPERS SHALL BE SIZED IN ACCORDANCE WITH 2014
 FBC-PLUMBING TABLE 1106.7. INDICATE THE HEAD IN INCHES
 IN THE CALCULATIONS.
 5) SHT.A2.2 - SHOW THE DIMENSIONS OF THE OVERFLOW
 SCUPPERS ON THE PLANS.
 6) SUBMIT DETAILS ON THE CANOPY DOWNSPOUTS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 7) SHT. A5.1 - DETAIL #3 - SHOW THE REQUIRED KNEE AND
 TOE CLEARANCES FOR THE LAVATORY PER 2014
 FBC-ACCESSIBILITY SEC. 306.
 8) SHT. A5.1 - DETAIL #4 - THE WATER CLOST SHALL BE
 16"- 18" TO THE CENTER FROM THE SIDE WALL PER 2014
 FBC-ACCESSIBILITY, SEC.604.2.
 9) SHT. A8.0 - EQUIPMENT #'S 113,195, 196, & 306 APPEAR
 HAVE THE OPERABLE PARTS OF THE EQUIPMENT OUTSIDE THE
 MAXIMUM REACH RANGES REQUIRED IN 2014 FBC SECS.227, 308
 & 309. INDICATE THE MAXIMUM WIDTH OF THE OBSTRUCTION
 FOR ALL EQUIPMENT ON THE COUNTERS.( SHOW THE DISTANCE
 THAT THE EQUIPMENT IS SET BACK FROM THE EDGE OF THE
 COUNTER. THIS WILL DETERMINE THE WIDTH OF THE
 "OBSTRUCTION." ) REFER TO 2014 FBC-ACCESSIBILITY,
 FIGURE 308.3.2.
 10.) SHT. P1.0 & P1.1- THE PLANS REFER TO CIVIL
 DRAWINGS FOR THE CONTINUATION OF THE 4' SEWER FROM THE
 ADJACENT TENANT SPACE AND ALSO FOR THE CONTINUATION OF
 THE WATER AND SEWER FORM THE 7-11. THERE ARE NO CIVIL
 DRAWINGS WITH THESE PLANS. CLARIFY.
 11) SHOW THE TERMINATION POINT OF THE RELIEF VALVE AND
 THE PAN DRAIN FROM THE WATER HEATER. COMPLY WITH 2014
 FBC-PLUMBING SECS.504.6, 504.7-504.7.2.
 12) SHT. P1.3 - SIZE ALL SECTIONS OF THE VENTING
 SYSTEM, SIZE ALL STACKS (WET & DRY SECTIONS.) WPB
 AMEND. TO FBC SEC. 107.2.1.
 13) SHT. P1.3 - THE STACK FOR THE 3" HUB DRAIN FOR
 CONDENSATE STARTS AS 3", A SECTION OF THE VENT IS 1
 1/2", AND THEN 3" THROUGH THE ROOF. CLARIFY.
 14) IF THE DEVELOPED LENGTH OF THE HOT WATER PIPING
 FROM THE SOURCE OF HOT WATER EXCEEDS 50 FEET THEN A HOT
 WATER RECIRCULATION LINE SHALL BE INSTALLED PER 2014
 FBC-PLUMBING SEC.607.2.
 15) THE MAXIMUM TEMPERATURE OF HOT WATER TO LAVATORIES
 IN PUBLIC RESTROOMS SHALL NOT EXCEED 110 DEGREES. 2014
 FBC-ENERGY SEC. C404.3 & C404.8.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  