Plan Review Notes
Plan Review Notes For Permit 15080178
Permit Number 15080178
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-13 16:46:081ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080178
 8/13/15
  
 1) REFERENCE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION AND PROVIDE COMPLIANCE SUBMITTALS-
 CALCULATION OF HEATING AND COOLING LOADS:
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 2) PLEASE NOTE THAT THE CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DIVISION REQUIRES SEPARATE
 PERMITS FOR REFRIGERATION SYSTEMS, AND KTICHEN HOOD AND
 EXHAUST SYSTEMS.
 3) PROVIDE DUCT SEALING AND ATTACHMENT DETAILS IN
 COMPLIANCE WITH TABLE C403.2.7.2 FBC-14 ENERGY
 CONSERVATION, AND DUCT SUPPORT DETAILS IN COMPLIANCE
 WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS- 2005.
 4) SHEET M1.1: REFERENCE SECTION 301.15 FBC-14
 MECHANICAL AND PROVIDE THE DESIGN WIND PRESSURES FOR
 THE ROOF TOP EQUIPMENT INSTALLATIONS. THE DETAILS SHOWN
 ON THE PLAN ARE FOR THE RTU AND FLEXPACK INSTALLATIONS-
 PLEASE ALSO PROVIDE DETAILS FOR THE FLEXPACK GRAVITY
 VENTILATOR.
 5) M1.1: SUBMIT TWO COPIES OF A CURRENT FLORIDA PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE CONDENSER ROOF STAND
 REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. THE
 ENGINEER SHALL CIRCLE, HIGHLIGHT, OR OTHERWISE MARK ALL
 DETAILS, NOTES, ANCHOR AND FASTENER SCHEDULES
 APPLICABLE TO THE PROPOSED INSTALLATION.
 6) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE RTU'S AND
 FLEXPACK UNIT: SHOW THE TYPE AND SIZE OF CONDENSATE
 PIPES, PIPE RUNS, PIPE SUPPORTS, PIPE PROTECTION, AND
 CONDENSATE DISCHARGE LOCATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  