| Plan Review Notes For Permit 15080162 |
| Permit Number |
15080162 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-17 15:50:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE NEWLY CREATED EXITS SHALL COMPLY WITH NFPA 101, | | | CHAPTER 7, 7.4 NUMBER OF EXITS. | | | | | | 2) THE EXITS SHALL COMPLY WITH NFPA 101, CHAPTER 7, 7.5 | | | ARRANGEMENTS OF EXITS. | | | | | | 3) SHEET A3, THE MINIMUM EXIT SEPARATION IS NOT | | | INDICATED OF THE EXITS. THE TWO EXITS AT THE FRONT ARE | | | NOT SEPARATED ENOUGH TO BE QUILFIED AT TWO EXITS. A | | | THIRD EXIT IS REQUIRED. | | | | | | 4) SHEET A3, THE COMMON PATH OF TRAVEL ALONG THE NEWLY | | | CREATED REAR CORRIDOR APPEARS TO EXCEED 75'. PLEASE | | | PROVIDE GREATER DETAIL ON ALL COMMON PATHS OF TRAVEL. | | | | | | 5) PROVIDE THE PURPOSE AND FUNCTION OF THE ROLLING | | | DOORS. WILL THEY BE TIED INTO THE FIRE ALARM SYSTEM? |
|