| Plan Review Notes For Permit 15080162 |
| Permit Number |
15080162 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-01 10:26:04 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. THE NEC REQUIRES THAT THERE BE A DEDICATED SIGN | | | OUTLET ABOVE/ADJACENT TO EVERY PEDESTRIAN ENTRY DOOR. | | | 2. NEC REQUIRES THAT THERE BE A SHOW WINDOW OUTLET | | | ABOVE EVERY SHOW WINDOW FOR EVERY 12' OF OF WINDOW OR | | | PORTION THEREOF. | | | 3. NEC PROHIBIT ELECTRICAL PANELS FROM BEING INSIDE | | | BATHROOMS; THERE APPEARS TO BE A PANEL INSIDE THE MEN'S | | | ROOM. | | | 4. THE SUBMITTED PLANS ARE MISSING SHEET "E2", RISER | | | DIAGRAM AND PANEL SCHEDULES. | | | 5. THIS SHEET SHALL ALSO INCLUDE THE ELECTRICAL LOAD | | | CALCS, OTHERWISE THEY SHALL BE PROVIDED ELSEWHERE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|