| Plan Review Notes For Permit 15080160 |
| Permit Number |
15080160 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-19 16:56:30 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL. | | | | | | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) | | | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED | | | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY | | | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT | | | CODE. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.00(33) FOR: | | | A) PRECAST LINTELS AS SPECIFIED ON PLANS. | | | | | | B) FLAT ROOF. CLEARLY IDENTIFY SELECTED APPROVED | | | ASSEMBLY AND PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET THE | | | DESIGN PRESSURES FOR ALL THE ROOF ZONES. | | | | | | 3- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT | | | SIGNING AND SEALING) ABOVE PRODUCT APPROVALS. SEC. | | | 107.3.4.1 CITY AMENDMENTS. | | | | | | 4- SHEET S-3: SIMPSON CONNECTOR H10A SPECIFIED FOR THE | | | NEW ROOF IS NOT ADEQUATE FOR INSTALLATION TO THE | | | EXISTING CBS WALL. THIS IS A WOOD TO WOOD CONNECTOR. | | | REVISE AS REQUIRED. SEC. R801.2 OF 2010 | | | FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|