| Plan Review Notes For Permit 15080156 |
| Permit Number |
15080156 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-10 14:28:48 | BUILDING PROVISO: | | | DOORS 100, 100A & 105 TO HAVE ELECTRO-MAGNETIC LOCKS | | | SHOW COMPLIANCE WITH: | | | 2010 FBC-B 1008.1.9.8 ELECTROMAGNETICALLY LOCKED EGRESS | | | DOORS. | | | DOORS IN THE MEANS OF EGRESS IN BUILDINGS WITH AN | | | OCCUPANCY IN GROUP A, B, E, M, R-1 OR R-2, | | | AND DOORS TO TENANT SPACES IN GROUP A, B, E, M, R-1 OR | | | R-2, SHALL BE PERMITTED TO BE | | | ELECTROMAGNETICALLY LOCKED IF EQUIPPED WITH LISTED | | | HARDWARE THAT INCORPORATES A BUILT-IN SWITCH | | | AND MEET THE REQUIREMENTS BELOW: | | | | | | 1. THE LISTED HARDWARE THAT IS AFFIXED TO THE DOOR LEAF | | | HAS AN OBVIOUS METHOD OF OPERATION | | | THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS. | | | | | | 2. THE LISTED HARDWARE IS CAPABLE OF BEING OPERATED | | | WITH ONE HAND. | | | | | | 3. OPERATION OF THE LISTED HARDWARE DIRECTLY INTERRUPTS | | | THE POWER TO THE ELECTROMAGNETIC LOCK | | | AND UNLOCKS THE DOOR IMMEDIATELY. | | | | | | 4. LOSS OF POWER TO THE LISTED HARDWARE AUTOMATICALLY | | | UNLOCKS THE DOOR. | | | | | | 5. WHERE PANIC OR FIRE EXIT HARDWARE IS REQUIRED BY | | | SECTION 1008.1.10, OPERATION OF THE LISTED | | | PANIC OR FIRE EXIT HARDWARE ALSO RELEASES THE | | | ELECTROMAGNETIC LOCK. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|