Plan Review Notes
Plan Review Notes For Permit 15080126
Permit Number 15080126
Review Stop P
Sequence Number 1
Notes
Date Text
2015-08-20 09:30:451) SHT.A-1 - A FRACTIONAL NUMBER OF OCCUPANTS SHALL BE
 ROUNDED UP TO THE NEXT WHOLE NUMBER , NOT DOWN.
 THEREFORE, THE OCCUPANT LOAD SHALL BE 18, NOT 17.
 2) THIS IS A CHANGE OF OCCUPANCY CLASSIFICATION. TWO
 TOILET ROOMS ARE REQUIRED (ONE FOR MALES & ONE FOR
 FEMALES) PER THE 2014 FBC-EXISTING BUILDING CODE
 SEC.1010.1 AND 2014 PLUMBING CODE TABLE 403.1.
 3) A SERVICE SINK IS REQUIRED PER 2014 FBC-PLUMBING
 TABLE 403.1.
 4) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 TABLE 403.1 AND FOOTNOTE ( E) OF FBC-PLUMBING AND SEC.
 211.2. OF THE 22014 FBC-ACCESSIBILITY. SHOW THE
 LOCATION OF THE DRINKING FOUNTAINS ON THE PLAN AND THE
 CLEAR FLOOR SPACE PER FBC-ACCESSIBILITY SEC. SEC.602.2.
 5) SUBMIT MANUF. SPECIFICATIONS FOR THE PEDICURE
 CHAIRS. WPB AMEND. TO FBC SEC. 107.2.1.
 6) THE VENT FOR THE PEDICURE CHAIRS IS NOT TO CODE. THE
 VENT SHALL CONNECT TO THE HORIZONTAL DRAIN ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE PER 2014 FBC
 PLUMBING SEC.905.3.FLAT,DRY VENTS ARE NOT PERMITTED.
 7) THE SANITARY DRAINAGE TO THE PEDICURE SINKS DOES NOT
 MEET CODE AS DRAWN. CONSIDER PIPING THIS AS A CIRCUIT
 VENTING SYSTEM IN ACCORDANCE WITH 2014 FBC-PLUMBING.
 8) SHOW THE CONNECCTION POINT OF THE TO THE POINT OF
 SERVICE FOR THE POTABLE WATER LINE ON THE WATER RISER.
 WPB AMEND. TO 2014 FBC SEC. 107.2.1.
 9) CLEANOUTS ARE REQUIRED IN THE STACKS PER FPC SEC.
 708.3.4.
 10) SHOW PROVISIONS FOR THERMAL EXPANSION IN ACCORDANCE
 WITH FPC SEC. 607.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  