| 2015-08-20 09:30:45 | 1) SHT.A-1 - A FRACTIONAL NUMBER OF OCCUPANTS SHALL BE |
| | ROUNDED UP TO THE NEXT WHOLE NUMBER , NOT DOWN. |
| | THEREFORE, THE OCCUPANT LOAD SHALL BE 18, NOT 17. |
| | 2) THIS IS A CHANGE OF OCCUPANCY CLASSIFICATION. TWO |
| | TOILET ROOMS ARE REQUIRED (ONE FOR MALES & ONE FOR |
| | FEMALES) PER THE 2014 FBC-EXISTING BUILDING CODE |
| | SEC.1010.1 AND 2014 PLUMBING CODE TABLE 403.1. |
| | 3) A SERVICE SINK IS REQUIRED PER 2014 FBC-PLUMBING |
| | TABLE 403.1. |
| | 4) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER |
| | TABLE 403.1 AND FOOTNOTE ( E) OF FBC-PLUMBING AND SEC. |
| | 211.2. OF THE 22014 FBC-ACCESSIBILITY. SHOW THE |
| | LOCATION OF THE DRINKING FOUNTAINS ON THE PLAN AND THE |
| | CLEAR FLOOR SPACE PER FBC-ACCESSIBILITY SEC. SEC.602.2. |
| | 5) SUBMIT MANUF. SPECIFICATIONS FOR THE PEDICURE |
| | CHAIRS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 6) THE VENT FOR THE PEDICURE CHAIRS IS NOT TO CODE. THE |
| | VENT SHALL CONNECT TO THE HORIZONTAL DRAIN ABOVE THE |
| | CENTERLINE OF THE HORIZONTAL DRAIN PIPE PER 2014 FBC |
| | PLUMBING SEC.905.3.FLAT,DRY VENTS ARE NOT PERMITTED. |
| | 7) THE SANITARY DRAINAGE TO THE PEDICURE SINKS DOES NOT |
| | MEET CODE AS DRAWN. CONSIDER PIPING THIS AS A CIRCUIT |
| | VENTING SYSTEM IN ACCORDANCE WITH 2014 FBC-PLUMBING. |
| | 8) SHOW THE CONNECCTION POINT OF THE TO THE POINT OF |
| | SERVICE FOR THE POTABLE WATER LINE ON THE WATER RISER. |
| | WPB AMEND. TO 2014 FBC SEC. 107.2.1. |
| | 9) CLEANOUTS ARE REQUIRED IN THE STACKS PER FPC SEC. |
| | 708.3.4. |
| | 10) SHOW PROVISIONS FOR THERMAL EXPANSION IN ACCORDANCE |
| | WITH FPC SEC. 607.3. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |